GE iBox Installation And Maintenance Manual page 33

Grid solutions
Table of Contents

Advertisement

GE Grid Solutions
Connecting Serial Interfaces
WESMAINT
The iBox is equipped with a WESMAINT port. By attaching a WESMAINT cable
Port
between the WESMAINT port and your PC, the iBox can:
Provide local maintenance and diagnostic functionality
Download configuration data from the optional SGConfig software
With the cable connected, you can also upload diagnostic and operational
information to the PC.
The WESMAINT interface supports RS-232 signaling and normally operates at a
fixed rate of 9600 bps.
WESMAINT
To connect to a PC, use a WESMAINT cable (GE part number 977-0048/96), or
Cable
equivalent.
The schematic for this cable is shown below:
Terminal - DB-9 Female
Standard
The iBox has three serial communications ports: COM1, COM2, and COM3
Serial
All COM ports have the following standard characteristics:
Interfaces
Female DB-9-F style connectors
RS-232 and RS-485 are supported on the same physical connector.
GE Information
1
N/C
2
RXD
TXD
3
4
N/C
COM
5
6
N/C
7
N/C
N/C
8
9
GND
Installation and Maintenance Guide
WESMAINT - DB-9 Male
1
2
3
4
5
6
7
8
9
994-0047-5.10-4
iBox/iBox Kit
COM
N/C
TXD
RXD
N/C
N/C
N/C
N/C
N/C
Continued on next page