GE iBox Installation And Maintenance Manual page 147

Grid solutions
Table of Contents

Advertisement

GE Grid Solutions
Technical Specifications – iBox Kit
Digital Inputs
Digital
Outputs
Switching Characteristics
GE Information
Up to eight bipolar optically isolated (2000 V
General
250 V rated compression termination consisting of a
header and removable plugs suitable for 12 – 24 AWG
Physical
wire 0.01A/150V
Burden
Wetting Options
Up to four relay outputs, configured as either:
General
250 V rated compression termination consisting of a
header and removable plugs suitable for 12 – 24 AWG
Physical Connection
wire rated for 6A/150V
Security features
Control Voltage
External
Maximum Carrying
6 A
Current
Installation and Maintenance Guide
, continued
From 1.9 mA to 5.5 mA
Max. power dissipation is 0.5 W per input
External wetting - for all input options
Modes of operation:
Dry contact and voltage sense
24 VDC, 48 VDC, and 110/125 VDC
4 trip/close pairs or
2 trip/close pairs and 2 Form A contacts
Separate Master Trip and Master Close relays
Single point of failure integrity, select-before-operate
(SBO) functionality.
Remote/Local jumper JP2
35 W breaking @ 150 VDC
180 W breaking @ 30 VDC
994-0047-5.10-4
iBox/iBox Kit
)
rms
Continued on next page
147

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ibox kit

Table of Contents