GE iBox Installation And Maintenance Manual page 53

Grid solutions
Table of Contents

Advertisement

GE Grid Solutions
Digital Input Configuration
Digital Input
Field wiring for all digital input variants are made through the iBox's terminal
Field
blocks, separable in pairs.
Connections
Digital Input
The digital input is wetted (or turned ON) by closing a contact across the two input
Wetting
termination points. The voltage that is switched at the input terminals is supplied by
Selection
an external source. The external power source is connected to terminal block TB-10,
positions 1 and 2, as shown below.
!
All eight digital inputs are bipolar. Use care when connecting multiple external
power sources, since the digital inputs have common returns.
Wiring
This diagram illustrates the DC input connections, from Input #1 (TB2) through
Diagram:
Input #8 (TB9). TB10 accepts DC voltages of either polarity. The input voltage level
Dry Contact
to TB10 is determined by the purchased option.
Operation
GE Information
TB2
TB9
2
1
2
1
Input #1
Input #8
994-0047-5.10-4
Installation and Maintenance Guide
TB10
2
1
+/- V
External Wetting
Power Supply
iBox/iBox Kit
53