GE iBox Installation And Maintenance Manual page 148

Grid solutions
Table of Contents

Advertisement

iBox/iBox Kit
Installation and Maintenance Guide
Technical Specifications – iBox Kit
AC Analog
Analog Input Options
Inputs
(optional)
Nominal PT Input Range
Short Duration Overload
DC Analog
Analog Input Options
Inputs
(optional)
148
Frequency
Measurement Range
Accuracy
Continuous Overload
Withstand
Withstand
Surge Withstand
True RMS Sampling
Isolation
Burden
A/D Resolution
Nominal DC Voltage
Input Range Options
Nominal DC Current
Input Range Options
Accuracy
994-0047-5.10-4
, continued
V
, I
, Phase Angle, Frequency, Power Factor, Real
RMS
RMS
Power (W), Reactive Power (VAR), Apparent Power (VA),
Watt-Hour
0 to 150VLN or 250VLL
50/60 Hz
0 to 125% of nominal
0.3%
200% of nominal
100 A for 3 seconds
As per IEEE C37.90.1, ANSI C62.41
64 samples per cycle
2500 VAC/60 Hz
Voltage and Current: 0.1 VA max
Power Supply: 6 VA max
Two DC analog inputs, or eight DC analog inputs
14 bits plus sign
±1 VDC, ±5 VDC or ±10 VDC
±20 mA or 4-20 mA
±0.2% of full scale @ 25
C
o
GE Grid Solutions
GE Information

Hide quick links: