Serial Communications
Protocol
Serial Gate-
OMRON components
way (conver-
(CompoWay/F-compatible devices)
sion to
CompoWay/
F) (unit ver-
sion 3.0 or
later only)
FINS
CompoWay/F
Serial commu-
nications path
OMRON components
Serial PLC
CJ1M CPU Unit
Polling Unit
Links (CJ1M
only)
CJ1W-CIF11
connected to
RS-232C port
(See note.)
CJ1M CPU Unit
Polled Unit
CJ1M CPU Unit
Polling Unit
RS-232C
CJ1M CPU Unit
Polled Unit
Connections
NS-series PT
PLC
Serial Gateway
RS-422A/485
For NS-series PT:
NS-AL002
CJ1M CPU Unit
Polled Unit
8 Units max.
Here, we will describe Host Link and No-protocol communications.
Note The CJ1W-CIF11 is not insulated and the total transmission distance is 50
meters max. If the total transmission distance is greater than 50 meters, use
the insulated NT-AL001 and do not use the CJ1W-CIF11. If only the NT-AL001
is used, the total transmission distance can is 500 meters max.
Description
Converts received FINS com-
mands into CompoWay/F com-
mands and transfers them on the
serial communications path.
Up to ten words per Unit can be
shared by up to nine CPU Units,
including one Polling Unit and
eight Polled Units.
An RS-422A Converter can be
connected to the RS-232C port on
each CPU Unit to communicate
via RS-422A/485, or two CPU
Units can communicate via an RS-
232C connection.
The Serial PLC Links can also
include PTs as Polled Units via NT
Links (1:N) combined with CJ1M
CPU Units.
Section 6-3
Ports
Peripheral
RS-232C
OK
OK
Not allowed OK