Manipulating Files
Transferring without a
Parameter Area File
(CS/CJ-series CPU Unit
Ver. 2.0 or Later Only)
File
File name
Program File
REPLACE.OBJ
Note: CS/CJ-series
CPU Unit Ver. 2.0 or
later only
Parameter Area
File
Data File
REPLACE.IOM
Note: CS/CJ-series
CPU Unit Ver. 2.0 or
later only
REPLCDM.IOM
Note: CS/CJ-series
CPU Unit Ver. 2.0 or
later only
REPLCE@.IOM
Note: CS/CJ-series
CPU Unit Ver. 2.0 or
later only
4. If DIP switch pin 7 is turned ON and pin 8 is turned OFF to use the simple
backup function, the simple backup function will take precedence even if
pin 2 is also ON. In this case, the BACKUP@@ files will be transferred to
the CPU Unit but the automatic transfer at startup files will not be trans-
ferred. (Not supported by CS-series CS1 CPU Units that are pre-EV1.)
5. The automatic transfer at startup function can be used together with the
program replacement function. The Replacement Start Bit (A65015) can
be turned ON from program that is automatically transferred at startup to
replace it with another program.
6. The automatic transfer function at startup and total program replacement
using Auxiliary Area bits can be used together, i.e., the program automat-
ically transferred to the CPU Unit at startup can contain programming to
manipulate the Auxiliary Area bits to replace the program with another one.
Use the following file names.
Program file: REPLACE.OBJ
Parameter area file: Not required and not transferred regardless of the file
name.
Data files: REPLACE.IOM, REPLCDM.IOM, REPLCE@.IOM
CPU Unit
User program
I/O memory
Parameter
data
Write at startup
The contents of this file are automatically transferred and
overwrite the entire user program including CPU Unit task
attributes.
Not transferred regardless of the file name.
DM words allocated to Special I/O Units, CPU Bus Units,
and Inner Boards (CS Series only).
The contents of this file are automatically transferred to
the DM Area beginning at D20000 when power is turned
ON.
General-purpose DM words
The contents of this file are automatically transferred to
the DM Area beginning at D00000 when power is turned
ON.
General-purpose DM words
The contents of this file are automatically transferred to
the EM Area beginning at E@_00000 when power is
turned ON. @ indicates the bank number.
Front panel DIP switch pin 2 ON
Memory Card
Must contain the following:
User program file (REPLACE.OBJ)
May contain the following:
I/O memory files (REPLACE.IOM,
REPLCDM.IOM, REPLCE.IOM)
At startup
Section 5-2
Required for
automatic transfer
Required on Memory
Card.
Not required.
Not required on
Memory Card.
229