Serial Communications
Serial Gateway Specifications
Converting FINS to CompoWay/F
FINS message
CPU Unit
(CMND(490)
FINS header
instruction) or
CompoWay/F command encapsulated
PT (Program-
using FINS command 2803 hex
mable Termi-
nal)
(Via network or CPU bus)
294
Item
Conversion source
FINS command (received via FINS network, Host Link FINS,
peripheral bus, NT links, or CPU bus)
Conversion function
Received FINS commands are converted according to the fol-
lowing values before sending to the serial port (peripheral port
or RS-232C port) of the CPU Unit.
2803 hex: Removes FINS header and converts to CompoWay/
F command
After conversion
CompoWay/F commands
Serial communica-
1:N half-duplex communications
tions method
Maximum number of
31 slaves
connected Units
Supported serial
Serial Gateway mode
communications
modes
Response timeout
The time is monitored from when a message converted to
monitoring
CompoWay/F protocol using the Serial Gateway is sent until a
response is received (enabled in Serial Gateway mode or pro-
tocol macro mode).
Default: 5 s; Setting range: 0.1 to 25.5 s
Note If a timeout occurs, the FINS end code is returned to the
Send delay
None
OMRON Components connected serially to the CPU Unit's RS-232C port or
peripheral port via CompoWay/F can be accessed from the PLC or PT using
CompoWay/F commands enclosed in FINS messages.
• Sent FINS message: FINS header + FINS command code 2803 hex +
CompoWay/F command
• Message after conversion: CompoWay/F command
2803
CompoWay/F command
For details on FINS command code 2803 hex, refer to the Communications
Commands Reference Manual (W342).
Details
source of the FINS command (0205 hex: Response tim-
eout).
CompoWay/F command
CPU Unit's
RS-232C or
CompoWay/F command
peripheral port
Section 6-3
CompoWay/F
-compatible
OMRON
Component