Omron CS1G/H-CPUxx-EV1 Programming Manual page 236

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxx-EV1:
Table of Contents

Advertisement

File Memory
Backup Files (Not
Supported by CS-series
CS1 CPU Units That Are
Pre-EV1)
Type
1
Name
Data file
BACKUP
BACKUPIO
BACKUPDM .IOM
BACKUPE@
Program file
BACKUP
Parameter file
Unit/Board
BACKUP@@
(where @@ is
backup files
(CS1-H, CJ1-
the unit
H, or CJ1M
address of
CPU Units
the
only)
Unit/Board
being backed
up)
Symbol table
BKUPSYM
files (See note
1.)
Comment files
BKUPCMT
(See note 1.)
Program index
BKUPPRG
files (See note
1.)
200
The files in the following table are created automatically when data is trans-
ferred to and from the Memory Card during backup operation.
Extension
Description
.IOM
DM Area words allo-
cated to Special I/O
Units, CPU Bus
Units, and Inner
Boards (CS Series
only)
.IOR
I/O memory data
areas
General-purpose DM
Area
.IOM
General-purpose EM
Area
.OBJ
Entire user program
.STD
PLC Setup, regis-
tered I/O table, rout-
ing tables, CPU Bus
Unit settings
.PRM
Data for specific Unit
or Board
.SYM
Global symbol
tables, local symbol
tables, and automati-
cally allocated area
setup data
.CMT
Rung comments and
comments
.IDX
CX-Programmer
section names, sec-
tion comments, and
program comments.
• Contains DM data from D20000 to D32767.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
• Contains all of the data in the CIO, WR, HR, and
AR data areas as well as timer/counter Comple-
tion Flags and PVs.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
• Contains DM data from D00000 to D19999.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
Contains all of the EM data for EM bank @ with
addresses ranging from E@_00000 to E@_32767.
(The maximum bank number depends upon the
model of CPU Unit being used.)
This file must exist on the Memory Card when read-
ing data from the Memory Card during backup.
• When data is backed up to the Memory Card, all
of the data in each EM bank is automatically writ-
ten to a separate file.
• Contains all cyclic and interrupt task programs as
well as task data for one CPU Unit.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
• Contains all initial settings for one CPU Unit.
• The user does not have to distinguish parameter
data in the file by type.
3
, etc.
• This file must exist on the Memory Card when
reading data from the Memory Card during
backup.
• Control backup data from one Unit or Board.
Refer to 5-2-6 Simple Backup Function for
details.
Includes the following data within the CX-Program-
mer's global/local symbol table:
Variables, addresses, data types, I/O comments
Includes the data set in the CX-Programmer's auto-
matic PLC address allocation settings.
CX-Programmer rung comments and comments.
CX-Programmer section delimiter data (The delim-
iter location, however, depends on the section
delimiter within the program.)
Section 5-1
Explanation
2

Advertisement

Table of Contents
loading