Manipulating Files
Program file
Parameter area
file
AUTOEXEC.OBJ AUTOEXEC.STD
None
REPLACE.OBJ
Ignored
1,2,3...
DIP Switch on the Front
Panel of the CPU Unit
232
More Than One Type of Data File
One or more of the follow-
ing: AUTOEXEC.IOM,
ATEXECDM.IOM, ATEX-
ECE@.IOM
Procedure
1. Turn OFF the PLC power supply.
2. Turn ON DIP switch pin 2 on the front panel of the CPU Unit. Be sure that
pins 7 and 8 are both OFF.
Note The simple backup function will take precedence over the automat-
ic transfer at startup function, so be sure that pins 7 and 8 are OFF.
3. Prepare a Memory Card as follows:
a) Transferring with a Parameter Area File
Insert a Memory Card containing the user program file (AUTOEX-
EC.OBJ), parameter area file (AUTOEXEC.STD), and/or the I/O mem-
ory files (AUTOEXEC.IOM, ATEXECDM.IOM, and ATEXECE@.IOM)
created with a CX-Programmer. (The program file and parameter area
file must be on the Memory Card. The I/O memory files are optional.)
b) Transferring without a Parameter Area File
Insert a Memory Card containing the user program file (RE-
PLACE.OBJ) and/or the I/O memory files (REPLACE.IOM, RE-
PLCDM.IOM, and REPLCE@.IOM) created with a CX-Programmer.
(The program file must be on the Memory Card. The I/O memory files
are optional.)
4. Turn ON the PLC power supply.
Note Automatic Transfer Failure at Startup
If automatic transfer fails at startup, a memory error will occur, A40115 will
turn ON, and the CPU Unit will stop. If an error occurs, turn OFF the power to
clear the error. (The error cannot be cleared without turning OFF the power.)
Pin(s)
Name
2
Automatic transfer at
startup pin
7 and 8
Simple backup pins
Data files
One or more of the follow-
ing: REPLACE.IOM,
REPLCDM.IOM,
REPLCE@.IOM
ON: Execute automatic transfer at startup.
OFF: Do not execute automatic transfer at startup.
Turn OFF both pins.
Section 5-2
Transferred/ Not
transferred
The following data files are
transferred:
AUTOEXEC.IOM, ATEX-
ECDM.IOM, ATEX-
ECE@.IOM
Not transferred.
The following data files are
transferred:
REPLACE.IOM,
REPLCDM.IOM,
REPLCE@.IOM
Setting