Omron CS1G/H-CPUxx-EV1 Programming Manual page 219

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxx-EV1:
Table of Contents

Advertisement

Interrupt Tasks
Power OFF Interrupt Task Execution
Cyclic task
Power
OFF
CPU reset
PLC Setup Settings for Power OFF Interrupt Task (Task Number: 1)
Address
Name
Bit 15 at +225
Power OFF
INTERRUPT
TASK
Bits 0 to 7 at
Power OFF
+225
Detection
Delay Time
External Interrupt Tasks: Tasks 0 to 255
Cyclic task
Power OFF interrupt task 1
Description
If bit 15 of +225 is ON, then a power OFF interrupt
task will start if power turns OFF.
Power OFF is recognized when this time plus the
default power OFF detection time (10 to 25 ms for AC
power supplies and 2 to 5 ms for DC power supplies)
expires.
External interrupt tasks can be received at any time.
Interrupt processing is performed at the CPU Unit in PLCs containing an Inner
Board (CS Series only), Special I/O Units, or CPU Bus Units. Settings don't
have to be made at the CPU Unit unless the program contains an external
interrupt task for a particular task number.
External interrupts are not supported by CJ1 CPU Units.
Example: The following example shows an external interrupt generated from
a CS1W-SCB@1 Serial Communications Board.
When the Serial Communications Board's response notification method is set
for interrupt notification (fixed number) or interrupt notification (reception case
Power OFF interrupt task ON/OFF
setting in PC Setup: ON
Settings
0: OFF,
1: ON
00 to 0A Hex: 0
to 10 ms (1-ms
units)
CPU Unit
Serial Communications Board
Interrupt
Section 4-3
Default
setting
0
00 Hex
183