Omron CS1G/H-CPUxx-EV1 Programming Manual page 304

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxx-EV1:
Table of Contents

Advertisement

Cycle Time/High-speed Processing
268
■ Outputting to Index Registers (IR)
If MAX(182) or MIN(183) is executed to output the I/O memory map address
of the word containing the minimum or maximum value to an index register,
the address will not be output to the index register and will be output to A595
and A596 instead. To store the address in an index register, use a Data Move
instruction (e.g., MOVL(498)) to copy the address in A595 and A596 to an
index register.
■ Conditions Flags
Conditions Flags will not be updated following execution of instructions pro-
cessed in the background. To access the Conditions Flag status, execute an
instruction that affects the Conditions Flags in the same way, as shown in the
following example, and then access the Conditions Flags.
Example:
MOV(021) affects the Equals and Negative Flags in the same way as
MAX(182), i.e., they both turn ON the Equals Flag for 0 and turn ON the Neg-
ative Flag if the MSB is ON. MOV(021) can thus be used to copy the results of
MAX(182) to the same address to manipulate the Conditions Flags so that the
status can be accessed.
Execution condition
000001
A20200
■ Outputting to Index Register IR00
If SRCH(181) is executed to output the I/O memory map address of the word
containing the matching value (the first word if there is more than one) to an
index register, the address will not be output to the index register and will be
output to A595 and A596 instead.
■ Outputting to Data Registers (DR) for SRCH(181)
If SRCH(181) is executed to output the matching data to a data register, the
data will not be output to the data register and will be output to A597 instead.
■ Matching Text Strings
If SRCH(181) finds matching data, it will not turn ON the Equals Flag, but will
turn on A59801 instead.
■ Instruction Errors
If an instruction execution error or illegal access error occurs for an instruction
being processed in the background, the ER or AER Flags will not be turned
MAX
Finds the maximum value in the
D01000
table data starting at D020000
D02000
and places it in D000000.
D00000
RSET
000000
SET
000001
Moves the contents of D000000
MOV
to D000000 to manipulate the
D00000
Conditions Flags.
D00000
W00000
Turns ON W00000 if the Equals
Flag is ON, i.e., if D000000
contains 0000 Hex.
Section 6-1

Advertisement

Table of Contents