Omron CS1G/H-CPUxx-EV1 Programming Manual page 160

Sysmac cs series; sysmac cj series
Hide thumbs Also See for CS1G/H-CPUxx-EV1:
Table of Contents

Advertisement

Data Control Instructions
Instruction
Symbol/Operand
Mnemonic
Code
DEAD ZONE
ZONE(682)
CONTROL
ZONE
@ZONE
682
S: Input word
C: 1st limit word
D: Output word
TIME-PROPOR-
TIONAL OUTPUT
TPO (685)
TPO
685
(CS/CJ-series
Unit Ver. 2.0 or
later only)
S: Input word
C: 1st parameter
word
R: Pulse Output
Bit
SCALING
SCL(194)
SCL
@SCL
194
S: Source word
P1: 1st parameter
word
R: Result word
124
Adds the specified bias to input data and outputs the result.
S
C
Positive bias (C+1)
D
Inputs the duty ratio or manipulated variable from the specified word,
converts the duty ratio to a time-proportional output based on the speci-
fied parameters, and outputs the result from the specified output.
S
C
R
Converts unsigned binary data into unsigned BCD data according to
the specified linear function.
S
R (unsigned BCD)
P1
R
Point A
Function
Output
Negative bias (C)
Scaling is performed according
to the linear function defined by
points A and B.
Point B
(BCD)
P
(BIN)
P1 + 1
P1 + 2
(BCD)
P1 + 3
(BIN)
S (unsigned binary)
Section 3-16
Location
Execution condition
Output
Required
Input
Output
Required
Output
Required
Converted
value
Converted
value

Advertisement

Table of Contents
loading

Table of Contents