Using File Memory
Automatically Transferring Files at Startup
1,2,3...
1,2,3...
250
Procedure when Transferring a Parameter Area File
1. Insert an initialized Memory Card into the CPU Unit.
2. Use a Programming Device to write the automatic transfer at startup files
to the Memory Card. These files include the program file (AUTOEX-
EC.OBJ), parameter area file (AUTOEXEC.STD), and I/O memory files
(AUTOEXEC.IOM, ATEXECDM.IOM and/or ATEXECE@.IOM).
Or
CX-Programmer
Note A user program and parameter area file must be on the Memory Card.
3. Turn OFF the PLC power supply.
4. Turn ON DIP switch pin 2 (automatic transfer at startup).
Note If pin 7 is ON and pin 8 is OFF, the backup function will be enabled
and will override the automatic transfer at startup function. Turn
OFF pins 7 and 8 for automatic transfer at startup.
5. Insert the Memory Card into the CPU Unit.
6. Turn ON the PLC power supply to read the file.
Procedure When Not Transferring a Parameter Area File
1. Insert an initialized Memory Card into the CPU Unit.
2. Use a Programming Device to write the automatic transfer at startup files
to the Memory Card. These files include the program file (REPLACE.OBJ)
and I/O memory files (REPLACE.IOM, REPLCDM.IOM, and/or RE-
PLCDE@.IOM).
Memory Card
Programming
Console
DIP switch pin 2 ON