GE G60 Instruction Manual page 94

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
each transmission.
NOTE
c) NETWORK
!
PATH: SETTINGS
PRODUCT SETUP
# NETWORK
#
These messages appear only if the G60 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the
TCP/UDP PORT NUMBER
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
5
behind a router). By setting a different
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP Port Number, or any User Map setting (when used with DNP) is changed,
it will not become active until power to the relay has been cycled (OFF/ON).
NOTE
Do not set more than one protocol to use the same
operation of those protocols.
WARNING
d) MODBUS PROTOCOL
!
PATH: SETTINGS
PRODUCT SETUP
# MODBUS PROTOCOL
#
The serial communication ports utilize the Modbus protocol, unless configured for DNP operation (see the DNP Protocol
description below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device
only. When using Modbus protocol on the RS232 port, the G60 will respond regardless of the
grammed. For the RS485 ports each G60 must have a unique address from 1 to 254. Address 0 is the broadcast address
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
5-12
!"
COMMUNICATIONS
IP ADDRESS:
0.0.0.0
SUBNET IP MASK:
MESSAGE
0.0.0.0
GATEWAY IP ADDRESS:
MESSAGE
0.0.0.0
# OSI NETWORK
MESSAGE
# ADDRESS (NSAP)
ETHERNET OPERATION
MESSAGE
MODE: Full-Duplex
. These settings are used only in advanced network configurations and should normally
TCP/UDP PORT NUMBER
!"
COMMUNICATIONS
MODBUS SLAVE
ADDRESS: 254
MODBUS TCP PORT
MESSAGE
NUMBER:
G60 Generator Management Relay
!"
NETWORK
Range: Standard IP address format
Only active if CPU Type 9G or 9H is ordered.
Range: Standard IP address format
Only active if CPU Type 9G or 9H is ordered.
Range: Standard IP address format
Only active if CPU Type 9G or 9H is ordered.
Range: Press the MESSAGE
NETWORK ADDRESS
9G or 9H is ordered.
Range: Half-Duplex, Full-Duplex
Only active if CPU Type 9G or 9H is ordered.
for a given protocol on each UR-series relay, the router can
TCP/UDP PORT NUMBER
!"
MODBUS PROTOCOL
Range: 1 to 254 in steps of 1
Range: 1 to 65535 in steps of 1
502
5 SETTINGS
!
key to enter the
. Only active if CPU Type
, as this will result in unreliable
MODBUS SLAVE ADDRESS
GE Multilin
OSI
pro-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ur series

Table of Contents