User-Programmable Self Tests - GE G60 Instruction Manual

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Table 5–2: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
LED 1 Operand
LED 2 Operand
LED 3 Operand
LED 4 Operand
LED 5 Operand
LED 6 Operand
LED 7 Operand
LED 8 Operand
LED 9 Operand
LED 10 Operand
LED 11 Operand
LED 12 Operand
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
5
# SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the Minor Alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, display target
messages. Moreover, they will not trigger the
minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter
7 for additional information on major and minor self-test alarms.
5-28
PARAMETER
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
Off
Off
Off
Off
!"

USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
MESSAGE
FUNCTION: Enabled
REMOTE DEVICE OFF
MESSAGE
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ANY MINOR ALARM
G60 Generator Management Relay
SETTING
PARAMETER
LED 13 Operand
Off
LED 14 Operand
Off
LED 15 Operand
Off
LED 16 Operand
Off
LED 17 Operand
SYNC 1 SYNC OP
LED 18 Operand
SYNC 2 SYNC OP
LED 19 Operand
Off
LED 20 Operand
Off
LED 21 Operand
Off
LED 22 Operand
Off
LED 23 Operand
Off
LED 24 Operand
Off
5.2.11 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled.
Valid for units equipped with Direct I/O Module.
Range: Disabled, Enabled.
Valid for units equipped with Direct I/O Module.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type D.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Valid for units equipped with CPU Type C or D.
Range: Disabled, Enabled.
or
messages. When in the "Enabled" mode,
ANY SELF-TEST
5 SETTINGS