User-Definable Displays - GE G60 Instruction Manual

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
a) MAIN MENU
!
PATH: SETTINGS
PRODUCT SETUP
# USER-DEFINABLE
# DISPLAYS
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the
USER DISPLAYS
tate text entry and Modbus Register data pointer options for defining the User Display content.
Once programmed, the user-definable displays can be viewed in two ways.
KEYPAD: Use the Menu key to select the
that only the programmed screens are displayed). The screens can be scrolled using the Up and Down keys. The dis-
play disappears after the default message time-out period specified by the
!"
DEFAULT MESSAGE TIMEOUT
USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
5
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the Down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The
INVOKE AND SCROLL
When the default timer expires (set by the
user displays. The next activity of the
play, not at the first user-defined display. The
b) USER DISPLAY 1(16)
!
PATH: SETTINGS
PRODUCT SETUP
# USER DISPLAY 1
#
5-32
!"

USER-DEFINABLE DISPLAYS

INVOKE AND SCROLL:
Off
# USER DISPLAY 1
MESSAGE
#
# USER DISPLAY 16
MESSAGE
#
menu (between the
USER DISPLAYS
setting.
input and the Down keypad key operate concurrently.
DEFAULT MESSAGE TIMEOUT
INVOKE AND SCROLL
INVOKE AND SCROLL
!"
USER-DEFINABLE DISPLAYS
DISP 1 TOP LINE:
DISP 1 BOTTOM LINE:
MESSAGE
DISP 1 ITEM 1
MESSAGE
0
DISP 1 ITEM 2
MESSAGE
0
DISP 1 ITEM 3
MESSAGE
0
DISP 1 ITEM 4
MESSAGE
0
DISP 1 ITEM 5:
MESSAGE
0
G60 Generator Management Relay
Range: FlexLogic™ operand
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
and
TARGETS
ACTUAL VALUES
menu item to access the first user-definable display (note
PRODUCT SETUP
setting), the relay will start to cycle through the
input stops the cycling at the currently displayed user dis-
pulses must last for at least 250 ms to take effect.
!
USER DISPLAY 1(16)
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
5 SETTINGS
5.2.15 USER-DEFINABLE DISPLAYS
top-level menus). The sub-menus facili-
!"
DISPLAY PROPERTIES
INVOKE AND SCROLL