B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 40)
ADDR
REGISTER NAME
6781
Stator Ground Stage 1 Pickup
6782
Stator Ground Stage 1 Pickup Delay
6783
Stator Ground Stage 1 Supervision
6784
Stator Ground Stage 2 Pickup
6785
Stator Ground Stage 2 Pickup Delay
B
6786
Stator Ground Stage 2 Supervision
6787
Stator Ground Block
6788
Stator Ground Target
6789
Stator Ground Event
678A
Reserved (5 items)
Split Phase Protection (Read/Write Grouped Setting)
67A0
Split Phase Protection Function
67A1
Split Phase Protection Source
67A2
Split Phase Protection Load Source
67A3
Split Phase Protection Phase A Pickup
67A4
Split Phase Protection Phase A Offset
67A5
Split Phase Protection Phase A Slope
67A6
Split Phase Protection Phase B Pickup
67A7
Split Phase Protection Phase B Offset
67A8
Split Phase Protection Phase B Slope
67A9
Split Phase Protection Phase C Pickup
67AA
Split Phase Protection Phase C Offset
67AB
Split Phase Protection Phase C Slope
67AC
Split Phase Protection Minimum Load
67AD
Split Phase Protection Mode
67AE
Split Phase Protection Delay
67AF
Split Phase Protection Block
67B0
Split Phase Protection Target
67B1
Split Phase Protection Events
67B2
Reserved (6 items)
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7007
Phase Undervoltage 1 Target
7008
Phase Undervoltage 1 Events
7009
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7046
Phase Overvoltage 1 Target
7047
Phase Overvoltage 1 Events
7048
Reserved (8 items)
B-26
RANGE
0 to 0.25
0 to 600
0.001 to 0.1
0 to 0.25
0 to 600
0.001 to 0.1
---
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 5
0.020 to 1.500
0 to 1
0 to 100
0.020 to 1.500
0 to 1
0 to 100
0.020 to 1.500
0 to 1
0 to 100
0 to 1
0 to 1
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 1
0 to 600
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
G60 Generator Management Relay
APPENDIX B
UNITS
STEP
FORMAT
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
pu
0.001
F001
s
0.01
F001
pu
0.0001
F001
---
---
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F167
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
%
0.1
F001
pu
0.01
F001
---
1
F225
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
---
1
F111
s
0.01
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F186
0 (Phase to Ground)
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
150
100
57
150
0
45
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC1)
0 (SRC1)
200
0
0
200
0
0
200
0
0
0
0 (Over)
0
0
0 (Self-Reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0 (Definite Time)
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
100
100
0
0 (Self-reset)
0 (Disabled)
0