GE G60 Instruction Manual page 375

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

APPENDIX B
F224
ENUMERATION: RATE TREND FOR FREQ RATE OF CHANGE
0 = Increasing, 1 = Decreasing, 2 = Bidirectional
F225
ENUMERATION: SPLIT PHASE PROTECTION MODE
0 = Over, 1 = Over-Under
F226
ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER
METHOD
0 = None, 1 = GSSE, 2 = GOOSE
F227
ENUMERATION: RELAY SERVICE STATUS
0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service
F230
ENUMERATION: DIRECTIONAL POLARIZING
0 = Voltage, 1 = Current, 2 = Dual
F231
ENUMERATION: POLARIZING VOLTAGE
0 = Calculated V0, 1 = Measured VX
F240
ENUMERATION: V/HZ CURVES
0 = Definite Time, 1 = Inverse A, 2 = Inverse B, 3 = Inverse C,
4 = FlexCurve™ A, 5 = FlexCurve™ B, 6 = FlexCurve™ C,
7 = FlexCurve™ D
F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit
descriptor and 1 bit for protection element to form a 16 bit value.
The combined bits are of the form: PTTTTTTDDDDDDDDD,
where P bit if set, indicates that the FlexLogic™ type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTT] and the values in round brackets indicate the descrip-
tor range.
[0] Off(0) this is boolean FALSE value
[0] On (1)This is boolean TRUE value
[2] CONTACT INPUTS (1 - 96)
[3] CONTACT INPUTS OFF (1-96)
[4] VIRTUAL INPUTS (1-64)
[6] VIRTUAL OUTPUTS (1-64)
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1-64)
GE Multilin
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1-64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1-64)
[14] REMOTE INPUTS (1-32)
[28] INSERT (Via Keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 64)
[52] SELF-TEST ERROR (see F141 for range)
[56] ACTIVE SETTING GROUP (1 to 6)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64 to 127] ELEMENT STATES
F400
UR_UINT16: CT/VT BANK SELECTION
bitmask
0
1
2
3
4
5
F500
UR_UINT16: PACKED BITFIELD
First register indicates input/output state with bits 0(MSB)-15(LSB)
corresponding to input/output state 1-16. The second register indi-
cates input/output state with bits 0-15 corresponding to input/out-
put state 17-32 (if required) The third register indicates input/
output state with bits 0-15 corresponding to input/output state 33-
48 (if required). The fourth register indicates input/output state with
bits 0-15 corresponding to input/output state 49-64 (if required).
The number of registers required is determined by the specific
data item. A bit value of 0 = Off, 1 = On
F501
UR_UINT16: LED STATUS
Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
the LED is on, 0 indicates the LED is off.
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element ID
X is bit [X mod 16] in register [X/16].
G60 Generator Management Relay
B.4 MEMORY MAPPING
bank selection
Card 1 Contact 1 to 4
Card 1 Contact 5 to 8
Card 2 Contact 1 to 4
Card 2 Contact 5 to 8
Card 3 Contact 1 to 4
Card 3 Contact 5 to 8
B
B-57

Advertisement

Table of Contents
loading

This manual is also suitable for: