GE G60 Instruction Manual page 346

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 40)
ADDR
REGISTER NAME
728C
Neutral Directional Overcurrent 1 Op Current
728D
Neutral Directional Overcurrent 1 Offset
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
728F
Reserved
7290
...Repeated for Neutral Directional Overcurrent 2
B
Negative Sequence Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
72A0
Negative Sequence Directional Overcurrent 1 Function
72A1
Negative Sequence Directional Overcurrent 1 Source
72A2
Negative Sequence Directional Overcurrent 1 Type
72A3
Neg Sequence Directional Overcurrent 1 Forward ECA
72A4
Neg Seq Directional Overcurrent 1 Forward Limit Angle
72A5
Neg Sequence Directional Overcurrent 1 Forward Pickup
72A6
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
72A7
Neg Sequence Directional Overcurrent 1 Reverse Pickup
72A8
Negative Sequence Directional Overcurrent 1 Target
72A9
Negative Sequence Directional Overcurrent 1 Block
72AA
Negative Sequence Directional Overcurrent 1 Events
72AB
Negative Sequence Directional Overcurrent 1 Offset
72AC
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
72AD
Reserved (3 items)
72B0
...Repeated for Neg Seq Directional Overcurrent 2
DCMA Inputs (Read/Write Setting) (24 modules)
7300
dcmA Inputs 1 Function
7301
dcmA Inputs 1 ID
7307
Reserved 1 (4 items)
730B
dcmA Inputs 1 Units
730E
dcmA Inputs 1 Range
730F
dcmA Inputs 1 Minimum Value
7311
dcmA Inputs 1 Maximum Value
7313
Reserved (5 items)
7318
...Repeated for dcmA Inputs 2
7330
...Repeated for dcmA Inputs 3
7348
...Repeated for dcmA Inputs 4
7360
...Repeated for dcmA Inputs 5
7378
...Repeated for dcmA Inputs 6
7390
...Repeated for dcmA Inputs 7
73A8
...Repeated for dcmA Inputs 8
73C0
...Repeated for dcmA Inputs 9
73D8
...Repeated for dcmA Inputs 10
73F0
...Repeated for dcmA Inputs 11
7408
...Repeated for dcmA Inputs 12
7420
...Repeated for dcmA Inputs 13
7438
...Repeated for dcmA Inputs 14
7450
...Repeated for dcmA Inputs 15
7468
...Repeated for dcmA Inputs 16
7480
...Repeated for dcmA Inputs 17
7498
...Repeated for dcmA Inputs 18
74B0
...Repeated for dcmA Inputs 19
74C8
...Repeated for dcmA Inputs 20
74E0
...Repeated for dcmA Inputs 21
74F8
...Repeated for dcmA Inputs 22
7510
...Repeated for dcmA Inputs 23
7528
...Repeated for dcmA Inputs 24
B-28
RANGE
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 1
0 to 90
40 to 90
0.05 to 30
40 to 90
0.05 to 30
0 to 2
0 to 65535
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
---
0 to 65535
---
0 to 6
-9999.999 to 9999.999
-9999.999 to 9999.999
0 to 65535
G60 Generator Management Relay
UNITS
STEP
FORMAT
---
1
F196
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F179
0 (Neg Sequence)
° Lag
1
F002
degrees
1
F001
pu
0.01
F001
degrees
1
F001
pu
0.01
F001
---
1
F109
---
1
F300
---
1
F102
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
---
F205
---
1
F001
---
---
F206
---
1
F173
---
0.001
F004
---
0.001
F004
---
1
F001
APPENDIX B
DEFAULT
0 (Calculated 3I0)
0
63
0
0 (Disabled)
0 (SRC 1)
75
90
5
90
5
0 (Self-reset)
0
0 (Disabled)
0
63
0
0 (Disabled)
"DCMA I 1"
0
"mA"
6 (4 to 20 mA)
4000
20000
0
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ur series

Table of Contents