User-Programmable Leds - GE G60 Instruction Manual

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
Configure the LED test to recognize User-Programmable Pushbutton 1 by making the following entries in the
!"
PRODUCT SETUP

USER-PROGRAMMABLE LEDS

"Enabled"
LED TEST FUNCTION:
"
PUSHBUTTON 1 ON
LED TEST CONTROL:
The test will be initiated when the User-Programmable Pushbutton 1 is pressed. The pushbutton should remain pressed for
as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then
automatically start Stage 2. At this point forward, test may be aborted by pressing the pushbutton.
APPLICATION EXAMPLE 2:
Assume one needs to check if any LEDs are "burned" as well as exercise one LED at a time to check for other failures. This
is to be performed via User-Programmable Pushbutton 1.
After applying the settings in Application Example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start Stage 2. Once Stage 2 has started, the pushbutton can be released. When
Stage 2 is completed, Stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.
c) TRIP AND ALARM LEDS
!
PATH: SETTINGS
PRODUCT SETUP
# TRIP & ALARM LEDS
#
MESSAGE
The Trip and Alarm LEDs are on LED Panel 1. Each indicator can be programmed to become illuminated when the
selected FlexLogic™ operand is in the Logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# LED 1
MESSAGE
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the Logic 1 state.
LEDs 1 through 24 inclusive are on LED Panel 2; LEDs 25 through 48 inclusive are on LED Panel 3.
Refer to the LED Indicators section in Chapter 4 for the locations of these indexed LEDs. This menu selects the operands
to control these LEDs. Support for applying user-customized labels to these LEDs is provided. If the
"Self-Reset" (default setting), the LED illumination will track the state of the selected LED operand. If the
is 'Latched', the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communi-
cations channel, or from any programmed operand, even if the LED operand state de-asserts.
GE Multilin
!
menu:
LED TEST
"
!"
USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off
!"
USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
G60 Generator Management Relay
5.2 PRODUCT SETUP
!"
TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
!"
USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
!
SETTINGS
5
setting is
LED X TYPE
setting
LED X TYPE
5-27