B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 17 of 40)
ADDR
REGISTER NAME
64D8
Reserved (4 items)
64DC
...Repeated for Overfrequency 2
64E8
...Repeated for Overfrequency 3
64F4
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
B
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
65CE
Power Swing Detect Delay 3 Pickup
65CF
Power Swing Detect Delay 4 Pickup
65D0
Power Swing Detect Seal In Delay
65D1
Power Swing Detect Trip Mode
65D2
Power Swing Detect Block
65D3
Power Swing Detect Target
65D4
Power Swing Detect Event
65D5
Power Swing Detect Shape
65D6
Power Swing Detect Quad Forward Middle
65D7
Power Swing Detect Quad Forward Outer
65D8
Power Swing Detect Quad Reverse Middle
65D9
Power Swing Detect Quad Reverse Outer
65DA
Power Swing Detect Outer Right Blinder
65DB
Power Swing Detect Outer Left Blinder
65DC
Power Swing Detect Middle Right Blinder
65DD
Power Swing Detect Middle Left Blinder
65DE
Power Swing Detect Inner Right Blinder
65DF
Power Swing Detect Inner Left Blinder
Accidental Energization (Read/Write Grouped Setting)
6660
Accidental Energization Function
6661
Accidental Energization Source
6662
Accidental Energization Arming Mode
6663
Accidental Energization OC Pickup
6665
Accidental Energization UV Pickup
6667
Accidental Energization Offline
6668
Accidental Energization Block
6669
Accidental Energization Target
666A
Accidental Energization Events
666B
Reserved (5 items)
Loss of Excitation (Read/Write Grouped Setting)
6680
Loss Of Excitation Function
6681
Loss Of Excitation Signal Source
6682
Loss Of Excitation Center 1
6683
Loss Of Excitation Radius 1
6684
Loss Of Excitation UV Supervision Enable 1
B-24
RANGE
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0.1 to 500
0 to 1
0 to 5
0 to 1
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0.1 to 300
0.1 to 300
0 to 1
G60 Generator Management Relay
UNITS
STEP
FORMAT
---
1
F001
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F514
---
1
F300
---
1
F109
---
1
F102
---
1
F085
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
---
1
F102
---
1
F167
---
1
F193
0 (UV AND OFFLINE)
---
0.001
F003
---
0.001
F003
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
ohm
0.01
F001
ohm
0.01
F001
---
1
F102
APPENDIX B
DEFAULT
0
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
30
50
17
9
17
400
0 (Delayed)
0
0 (Self-reset)
0 (Disabled)
0 (Mho Shape)
6000
7000
6000
7000
10000
10000
10000
10000
10000
10000
0 (Disabled)
0 (SRC 1)
300
500
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
800
1 (Enabled)