9 APPLICATION OF SETTINGS
b) ZONE 1 SETTING IN APPLICATION (A)
As the transformer is located between the potential source and the reach point for Zone 1, the reach impedance must
include the positive-sequence impedance of the transformer. In addition, the primary impedance must be re-calculated for
the voltage level of the VTs and CTs, and eventually, re-calculated to secondary quantities:
c) ZONE 3 SETTING IN APPLICATION (A)
As the transformer is not located between the potential source and the reach point for Zone 3, the reach impedance must
not include the positive-sequence impedance of the transformer. Because both VTs and CTs are located on the same side
as the intended reach point, no correction for the transformer ratio is required. The primary impedance must be only re-cal-
culated to secondary quantities:
d) ZONE 1 SETTING IN APPLICATION (B)
As the transformer is not located between the potential source and the reach point for Z1, the reach impedance must not
include the positive-sequence impedance of the transformer. The CTs are located on the other side of the transformer, thus
transformer ratio must be included:
e) ZONE 3 SETTING IN APPLICATION (B)
As the transformer is located between the potential source and the reach point for Zone 3, the reach impedance must
include the positive-sequence impedance of the transformer. The VTs are located on the other side of the transformer, thus
transformer ratio must be included:
Given the following for the system shown in the previous section:
= 30 Ω ∠85° (intended reach of Zone 1)
Z
X
= 0.06 Ω ∠88° (intended reach of Zone 3)
Z
H
n
= 8000:5 = 1600 (located at H)
CT
n
= 315000:120 = 2625 (located at X)
VT
Transformer: 13.8/315 kV, 150 MVA, 10%, delta/wye, 315 kV side lagging 30°
Transformer impedance:
The Zone 1 settings are:
"0.80"
PHS DIST Z1 REACH:
"85"
PHS DIST Z1 RCA:
PHS DIST Z1 XMFR VOL CONNECTION:
PHS DIST Z1 XMFR CUR CONNECTION:
GE Multilin
9.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS
V
(
(
)
)
×
------ -
Z
Z
at X
Z
=
+
1
T
x
V
n
CT
×
---------
Z
Z
=
3
H
n
VT
V
n
H
×
×
------ -
---------
Z
Z
=
1
X
V
n
X
V
(
(
)
)
×
------ -
Z
Z
at H
Z
=
+
3
T
H
V
2
(
)
10
13.8
(
)
×
--------- -
------------------ -
Z
at H
=
=
T
100
150
13.8
1600
×
---------- -
×
------------ -
Z
30
0.8011Ω 85°
=
=
1
315
2625
"None"
"Dy1"
G60 Generator Management Relay
n
2
H
CT
×
---------
n
X
VT
CT
VT
n
X
CT
×
---------
n
H
VT
0.127Ω 90°
(EQ 9.31)
(EQ 9.32)
(EQ 9.33)
(EQ 9.34)

9.2.2 EXAMPLE

(EQ 9.35)
9
(EQ 9.36)
9-15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ur series

Table of Contents