GE G60 Instruction Manual page 100

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
h) TFTP PROTOCOL
!
PATH: SETTINGS
PRODUCT SETUP
# TFTP PROTOCOL
#
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G60 over a network. The G60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the G60 contains a list and description of all available files (event records, oscillography, etc.).
i) IEC 60870-5-104 PROTOCOL
!
PATH: SETTINGS
PRODUCT SETUP
# IEC 60870-5-104
# PROTOCOL
5
The G60 supports the IEC 60870-5-104 protocol. The G60 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the G60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the G60 at one time.
The
NUMBER OF SOURCES IN MMENC1 LIST
are included in the M_ME_NC_1 (measured value, short floating point) Analog points list. This allows the list to be custom-
ized to contain data for only the sources that are configured.
The
IEC ------- DEFAULT THRESHOLD
responses containing M_ME_NC_1 analog data. These settings group the G60 analog data into types: current, voltage,
power, energy, and other. Each setting represents the default threshold value for all M_ME_NC_1 analog points of that
type. For example, in order to trigger spontaneous responses from the G60 when any current values change by 15 A, the
IEC CURRENT DEFAULT THRESHOLD
5-18
!"
COMMUNICATIONS
TFTP MAIN UDP PORT
NUMBER:
TFTP DATA UDP PORT 1
MESSAGE
NUMBER:
TFTP DATA UDP PORT 2
MESSAGE
NUMBER:
!"
COMMUNICATIONS
IEC 60870-5-104
FUNCTION: Disabled
IEC TCP PORT
MESSAGE
NUMBER: 2404
# IEC NETWORK
MESSAGE
# CLIENT ADDRESSES
IEC COMMON ADDRESS
MESSAGE
OF ASDU:
IEC CYCLIC DATA
MESSAGE
PERIOD:
NUMBER OF SOURCES
MESSAGE
IN MMENC1 LIST: 1
IEC CURRENT DEFAULT
MESSAGE
THRESHOLD: 30000
IEC VOLTAGE DEFAULT
MESSAGE
THRESHOLD: 30000
IEC POWER DEFAULT
MESSAGE
THRESHOLD: 30000
IEC ENERGY DEFAULT
MESSAGE
THRESHOLD: 30000
IEC OTHER DEFAULT
MESSAGE
THRESHOLD: 30000
setting allows the selection of the number of current/voltage source values that
settings are the values used by the G60 to determine when to trigger spontaneous
setting should be set to 15. Note that these settings are the default values of the dead-
G60 Generator Management Relay
!"
TFTP PROTOCOL
Range: 1 to 65535 in steps of 1
69
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
!"
IEC 60870-5-104 PROTOCOL
Range: Enabled, Disabled
Range: 1 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
0
Range: 1 to 65535 s in steps of 1
60 s
Range: 1 to 4 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ur series

Table of Contents