5 SETTINGS
!"
PATH: SETTINGS
GROUPED ELEMENTS
# LOSS OF
# EXCITATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
Figure 5–84: LOSS OF EXCITATION OPERATING CHARACTERISTICS
GE Multilin
!
!"
SETTING GROUP 1(6)

LOSS OF EXCITATION

LOSS OF EXCITATION
FUNCTION: Disabled
LOSS OF EXCITATION
SOURCE: SRC 1
LOSS OF EXCITATION
CENTER 1: 10.00 ohm
LOSS OF EXCITATION
RADIUS 1: 8.00 ohm
EXCITATION V SUPV 1:
Enabled
LOSS OF EXCITATION
PKP DELAY1: 0.050 s
LOSS OF EXCITATION
CENTER 2: 12.00 ohm
LOSS OF EXCITATION
RADIUS 2: 10.00 ohm
LOSS OF EXCITATION
V SUPV 2: Enabled
LOSS OF EXCITATION
PKP DELAY2: 0.500 s
LOSS OF EXCITATION
UV SUPV: 0.700 pu
LOSS OF EXCIT BLK:
Off
LOSS OF EXCITATION
TARGET: Self-reset
LOSS OF EXCITATION
EVENTS: Disabled
X
G60 Generator Management Relay
5.5 GROUPED ELEMENTS
5.5.13 LOSS OF EXCITATION
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: 0.10 to 300.00 ohms in steps of 0.01
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.01
Range: 0.000 to 1.250 pu in steps of 0.001
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
R
C1
= Center of element 1 = (Zb + X'd) / 2
R1
= Radius of element 1 = Zb / 2
C2
= Center of element 2 = (Xd + X'd) / 2
R2
= Radius of element 2 = Xd / 2
Zb
= Base impedance of the machine
X'd
= Transient reactance of the machine
Xd
= Synchronous reactance of the machine
830711A1.CDR
5
5-131