B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 40)
ADDR
REGISTER NAME
Underfrequency (Read/Write Setting) (6 modules)
7E00
Underfrequency Function
7E01
Underfrequency 1 Block
7E02
Underfrequency 1 Minimum Current
7E03
Underfrequency 1 Pickup
B
7E04
Underfrequency 1 Pickup Delay
7E05
Underfrequency 1 Reset Delay
7E06
Underfrequency 1 Source
7E07
Underfrequency 1 Events
7E08
Underfrequency 1 Target
7E09
Reserved (8 items)
7E11
...Repeated for Underfrequency 2
7E22
...Repeated for Underfrequency 3
7E33
...Repeated for Underfrequency 4
7E44
...Repeated for Underfrequency 5
7E55
...Repeated for Underfrequency 6
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F06
Neutral Overvoltage 1 Target
7F07
Neutral Overvoltage 1 Events
7F08
Reserved (8 items)
7F10
...Repeated for Neutral Overvoltage 2
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30
Auxiliary Overvoltage 1 Function
7F31
Auxiliary Overvoltage 1 Signal Source
7F32
Auxiliary Overvoltage 1 Pickup
7F33
Auxiliary Overvoltage 1 Pickup Delay
7F34
Auxiliary Overvoltage 1 Reset Delay
7F35
Auxiliary Overvoltage 1 Block
7F36
Auxiliary Overvoltage 1 Target
7F37
Auxiliary Overvoltage 1 Events
7F38
Reserved (8 items)
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
B-30
RANGE
0 to 1
0 to 65535
0.1 to 1.25
20 to 65
0 to 65.535
0 to 65.535
0 to 5
0 to 1
0 to 2
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
G60 Generator Management Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F300
pu
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F167
---
1
F102
---
1
F109
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (Disabled)
0
10
5950
2000
2000
0 (SRC 1)
0 (Disabled)
0 (Self-reset)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0