5 SETTINGS

5.2PRODUCT SETUP

!
PATH: SETTINGS
PRODUCT SETUP
# PASSWORD
# SECURITY
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Two levels of password security are provided: Command and Setting. Operations under password supervision are:
COMMAND:
changing the state of virtual inputs, clearing the event records, clearing the oscillography records,
changing the date and time, clearing energy records, clearing the data logger, user-programmable
pushbuttons
SETTING:
changing any setting, test mode operation
The Command and Setting passwords are defaulted to "Null" when the relay is shipped from the factory. When a password
is set to "Null", the password security feature is disabled.
Programming a password code is required to enable each access level. A password consists of 1 to 10 numerical charac-
ters. When a
CHANGE ... PASSWORD
1.
ENTER NEW PASSWORD: ____________
2.
VERIFY NEW PASSWORD: ____________
3.
NEW PASSWORD HAS BEEN STORED
To gain write access to a "Restricted" setting, set
change the setting and follow the prompt to enter the programmed password. If the password is correctly entered, access
will be allowed. If no keys are pressed for longer than 30 minutes or control power is cycled, accessibility will automatically
revert to the "Restricted" level.
If an entered password is lost (or forgotten), consult the factory with the corresponding
The G60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The
UNAUTHORIZED ACCESS
command. Therefore, to apply this feature with security, the command level should be password-protected.
ALARMS
The operand does not generate events or targets. If these are required, the operand can be assigned to a digital element
programmed with event logs and/or targets enabled.
If the
and
SETTING
COMMAND
and settings.
NOTE
When EnerVista UR Setup is used to access a particular level, the user will continue to have access to that
level as long as there are open windows in the EnerVista UR Setup software. To re-establish the Password
Security feature, all windows must be closed for at least 30 minutes.
NOTE
GE Multilin
!

PASSWORD SECURITY

ACCESS LEVEL:
Restricted
CHANGE COMMAND
PASSWORD: No
CHANGE SETTING
PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ----------
ENCRYPTED SETTING
PASSWORD: ----------
setting is set to "Yes", the following message sequence is invoked:
ACCESS LEVEL
operand is reset with the
COMMANDS
passwords are identical, this one password allows access to both commands
G60 Generator Management Relay
5.2.1 PASSWORD SECURITY
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
Range: No, Yes
Range: No, Yes
Range: 0 to 9999999999
Note: ---------- indicates no password
Range: 0 to 9999999999
Note: ---------- indicates no password
to "Setting" and then change the setting, or attempt to
ENCRYPTED PASSWORD
UNAUTHORIZED ACCESS
!"
!"
CLEAR RECORDS
5.2 PRODUCT SETUP
5
.
FlexLogic™ operand is
RESET UNAUTHORIZED
5-7