9.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS
The Zone 3 settings are:
PHS DIST Z3 REACH:
"89"
PHS DIST Z3 RCA:
PHS DIST Z3 XMFR VOL CONNECTION:
PHS DIST Z3 XMFR CUR CONNECTION:
9
9-16
(
Z
0.127 90°
0.006 88°
=
+
3
"2.60"
"Yd11"
"None"
G60 Generator Management Relay
315
1600
)
×
×
---------- -
------------ -
2.601Ω 89.4°
=
13.8
2625
9 APPLICATION OF SETTINGS