GE G60 Instruction Manual page 154

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
b) PHASE DISTANCE
!"
PATH: SETTINGS
GROUPED ELEMENTS
# PHASE DISTANCE Z1
#
5
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. The phase quadrilateral distance function is comprised of a reac-
tance characteristic, right and left blinders, and 100% memory-polarized directional and current supervising characteristics.
When set to "Non-directional", the mho function becomes an offset mho with the reverse reach controlled independently
from the forward reach, and all the directional characteristics removed. When set to "Non-directional", the quadrilateral
function applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for addi-
tional information.
5-72
!
SETTING GROUP 1(6)
PHS DIST Z1
FUNCTION: Disabled
PHS DIST Z1 DIR:
MESSAGE
Forward
PHS DIST Z1 XFMR VOL
MESSAGE
CONNECTION: None
PHS DIST Z1 XFMR CUR
MESSAGE
CONNECTION: None
PHS DIST Z1
MESSAGE
REACH:
PHS DIST Z1
MESSAGE
RCA: 85°
PHS DIST Z1 REV
MESSAGE
REACH: 2.00 ohms
PHS DIST Z1 REV
MESSAGE
REACH RCA: 85°
PHS DIST Z1
MESSAGE
COMP LIMIT: 90°
PHS DIST Z1
MESSAGE
DIR RCA: 85°
PHS DIST Z1
MESSAGE
DIR COMP LIMIT: 90°
PHS DIST Z1
MESSAGE
SUPV: 0.200 pu
PHS DIST Z1 VOLT
MESSAGE
LEVEL: 0.000 pu
PHS DIST Z1
MESSAGE
DELAY: 0.000 s
PHS DIST Z1 BLK:
MESSAGE
Off
PHS DIST Z1
MESSAGE
TARGET: Self-reset
PHS DIST Z1
MESSAGE
EVENTS: Disabled
G60 Generator Management Relay
!"
!"
DISTANCE
PHASE DISTANCE Z1(Z3)
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
Yd5, Yd7, Yd9, Yd11
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
Yd5, Yd7, Yd9, Yd11
Range: 0.02 to 250.00 ohms in steps of 0.01
2.00 ohms
Range: 30 to 90° in steps of 1
Range: 0.02 to 250.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.000 to 5.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS