Records; User-Programmable Fault Reports; Event Records; Oscillography - GE G60 Instruction Manual

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

6 ACTUAL VALUES

6.4RECORDS

!"
PATH: ACTUAL VALUES
RECORDS
# USER-PROGRAMMABLE
# FAULT REPORT
MESSAGE
MESSAGE
This menu displays the User-Programmable Fault Report actual values. See the User-Programmable Fault Report section
in Chapter 5 for additional information on this feature.
!"
PATH: ACTUAL VALUES
RECORDS

# EVENT RECORDS

#
MESSAGE
MESSAGE
MESSAGE
The Event Records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. Refer to the
!"
PATH: ACTUAL VALUES
RECORDS

# OSCILLOGRAPHY

#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
'cycles per record' value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillogra-
phy section of Chapter 5 for further details.
A trigger can be forced here at any time by setting "Yes" to the
menu for clearing the oscillography records.
CLEAR RECORDS
GE Multilin
!
USER-PROGRAMMABLE FAULT REPORT
NEWEST RECORD
NUMBER: 0
LAST CLEARED DATE:
2002/8/11 14:23:57
LAST REPORT DATE:
2002/10/09 08:25:27
!"
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
"
COMMANDS
CLEAR RECORDS
!"
OSCILLOGRAPHY
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
CYCLES PER RECORD:
0.0
LAST CLEARED DATE:
2000/07/14 015:40:16
G60 Generator Management Relay

6.4.1 USER-PROGRAMMABLE FAULT REPORTS

EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
menu for clearing event records.
Range: No, Yes
command. Refer to the
FORCE TRIGGER?
6.4 RECORDS
6.4.2 EVENT RECORDS
6
6.4.3 OSCILLOGRAPHY
!"
COMMANDS
6-17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ur series

Table of Contents