Advertisement

5 SETTINGS
Three zones of phase distance protection are provided. Each zone is configured individually through its own setting menu.
All of the settings can be independently modified for each of the zones except:
1.
The
setting (common for the phase distance elements of all zones as entered under
SIGNAL SOURCE
!
GROUPED ELEMENTS
SETTING GROUP 1(6)
2.
The
setting (common for the phase distance elements of all zones as entered under
MEMORY DURATION
!
GROUPED ELEMENTS
SETTING GROUP 1(6)
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in Chapter 8: Theory of Operation.
Ensure that the
PHASE VT SECONDARY VOLTAGE
menu) is set correctly to prevent improper operation of associated memory action.
VOLTAGE BANK
WARNING
PHS DIST Z1 DIR: All zones are reversible. The forward direction is defined by the
the reverse direction is shifted 180° from that angle. The non-directional zone spans between the forward reach imped-
ance defined by the
PHS DIST Z1 REACH
and
DIST Z1 REV REACH
PHS DIST Z1 REV REACH RCA
Figure 5–37: DIRECTIONAL MHO DISTANCE CHARACTERISTIC
Figure 5–38: NON-DIRECTIONAL MHO DISTANCE CHARACTERISTIC
GE Multilin
!"
).
DISTANCE
!"
).
DISTANCE
setting (see the
and
settings, and the reverse reach impedance defined by
PHS DIST Z1 RCA
as illustrated below.
X
COMP LIMIT
DIR COMP LIMIT
DIR COMP LIMIT
DIR RCA
RCA
X
RCA
REV REACH
RCA
G60 Generator Management Relay
5.5 GROUPED ELEMENTS
!"
SETTINGS
SYSTEM SETUP
PHS DIST Z1 RCA
R
837720A1.CDR
COMP LIMIT
R
837800A1-X1.CDR
!"
SETTINGS
!"
SETTINGS
!
!"
AC INPUTS
setting, whereas
PHS
5
5-73