5 SETTINGS
!"
PATH: SETTINGS
CONTROL ELEMENTS

# SELECTOR SWITCH 1

#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The Selector Switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The 3-bit control input allows setting
the selector to the position defined by a 3-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current 3-bit word (user setting).
Basic alarm functionality alerts the user under abnormal conditions; e.g. the 3-bit control input being out of range.
SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (Position 1). When using a direct 3-bit
control word for programming the selector to a desired position, the change would take place only if the control word is
within the range of 1 to the
setting the
SELECTOR ALARM
SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in
the following two ways. When the
GE Multilin
!"
SELECTOR SWITCH
SELECTOR 1 FUNCTION:
Disabled
SELECTOR 1 FULL
RANGE: 7
SELECTOR 1 TIME-OUT:
5.0 s
SELECTOR 1 STEP-UP:
Off
SELECTOR 1 STEP-UP
MODE: Time-out
SELECTOR 1 ACK:
Off
SELECTOR 1 3BIT A0:
Off
SELECTOR 1 3BIT A1:
Off
SELECTOR 1 3BIT A2:
Off
SELECTOR 1 3BIT
MODE: Time-out
SELECTOR 1 3BIT ACK:
Off
SELECTOR 1 POWER-UP
MODE: Restore
SELECTOR 1 TARGETS:
Self-reset
SELECTOR 1 EVENTS:
Disabled
. If the control word is outside the range, an alarm is established by
SELECTOR FULL RANGE
FlexLogic™ operand for 3 seconds.
SELECTOR STEP-UP MODE
G60 Generator Management Relay
5.6 CONTROL ELEMENTS
!
SELECTOR SWITCH 1(2)
Range: Disabled, Enabled
Range: 1 to 7 in steps of 1
Range: 3.0 to 60.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: Time-out, Acknowledge
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Time-out, Acknowledge
Range: FlexLogic™ operand
Range: Restore, Synchronize, Sync/Restore
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
is "Time-out", the setting specifies the required period of
5.6.3 SELECTOR SWITCH