With The Control Unit And The Analyser Box - TESTO 300 XXL Instruction Manual

Hide thumbs Also See for 300 XXL:
Table of Contents

Advertisement

Example measurement
Conducting a CO measurement in gas burners (flue gas path test)
with the control unit and analyser box
Function menu
Measurement menu
uCO on
Measurement menu
uCO off
24
CO limit for the rejection of a system (in relation to
undiluted flue gas): > 1000 ppm uCO
1 Activate the function menu with with the
one of the function keys. Select function key
with
2 Start measurement with
3 Measure undiluted CO with
Display of the function key changes to
4 Finish undiluted CO measurement with
Undiluted CO is saved.
5 Finish measurement with
and confirm with
.
PStart
.
uCO on
.
PStop
key and
uCO on
.
.
uCO off
.
uCO off