Flue Gas Measurement At Burners With Control Unit And Analyser Box - TESTO 300 XXL Instruction Manual

Hide thumbs Also See for 300 XXL:
Table of Contents

Advertisement

Measurement menu
Location
Measurement menu
1 sec
Function menu
Measurement menu
Measurement menu
with the control unit and the analyser box
Preparing for measurement
1 Specify new location and select (see page 41):
2 The four function keys of the control unit are freely
configurable with the functions of the function menu.
3 Activate the function menu with the
the function keys. Select function key
and confirm with
4 Start measurement with
5 Position the flue gas probe in the core current:
Seek flue gas temperature AT max, then fasten the probe
with the cone in this position.
If the flue gas probe is positioned vertically or at an angle
of up to 45°, falling drops of condensation can cause a
sudden drop in the temperature.
Remedy: Readjust flue gas probe.
6 When the readings no longer change, stop the pump.
Place flue gas probe in fresh air.
The readings are retained until the pump is next started.
Example measurement
Flue gas measurement at burners
Back to the measurement menu
.
.
PStart
key and one of
with
PStart
23