Abus SECVEST Installer Manual page 216

Hide thumbs Also See for SECVEST:
Table of Contents

Advertisement

Appendix
Extended SIA 3
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS
Extended SIA 3 V2
#AAAAAA|Ntihh:mm|idnnn|rinn|CCcc|AS
Whereby:
AAAAAA
Adjustable 6-digit account number (e.g. 123456).
"N"
New event (always N)
"ti"hh:mm/
Time (e.g. ti10:23/).
"id"nnn/
User number, when usable, otherwise not sent (e.g. id123/ or id6/)
"ri"nn/
Partition number (e.g. ri12/ or ri3).
CC
Event code (e.g. FA = Fire Alarm).
cc
Zone or control panel number, when usable, otherwise not sent (e.g. 23 or 5)
"A"S
Text description of the event, usually a description of the log book event
Note:
The alarm control panel
table above.
Example
The different formats for the SIA protocol appear as follows in the event of a fire alarm in zone 2 of partition 4 at 10:15
with the account number 10 for partition 4:
SIA1
SIA2
SIA3
Extended SIA3
Extended SIA3 V2
Note about Extended SIA3 V2:
Some S/W versions that work in the SIA recipients do not always recognise the "/" text separator. This may cause
problems. This incorrectly results in "mains fail" messages on the ARC (ESCC). This may occur when arming or
disarming the alarm control panel or when entering or exiting the Installer Mode.
Therefore, in version 2 of Extended SIA3, the "/" text separator has been replaced by a "|" text separator.
For example, the string will change from:
#000010|Nti10:15/ri4/FA2/AFire Zone 2
to:
#000010|Nti10:15|ri4|FA2|AFire Zone 2
If you are having problems with incorrect"mains fail" messages, try this extended SIA3 V2 option.
DC-09
The alarm control panel automatically uses the IP-based protocol DC-09 if the alarm control panel uses Ethernet
(LAN) as an outgoing communication path.
In doing so, the data from traditional protocols are packed into IP packages and transferred.
Note:
Details can be found in the DC-09 and DC-07 specification from SIA and in the corresponding standards that
are mentioned in these documents.
216
sends the characters that are between " and " shown above exactly as they are listed in the
#000010|NFA2
#000010|N/ri4/FA2
#000010|Nti10:15/ri4/FA2
#000010|AFire Zone 2
#000010|Nti10:15/ri4/FA2/AFire Zone 2
#000010|Nti10:15|ri4|FA2|AFire Zone 2