Ul609 Local Mercantile Premises/Local Mercantile Safe & Vault; Ul365 Police Station Connected Burglar Alarm; Ul1610 Central Station Burglary Alarm - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
UL609 Local Mercantile Premises/Local Mercantile Safe & Vault
1. All zones must be configured for EOLR supervision (*41=0). If 4190SN V-Plex devices are used, set field
*24 to "0" to enable tamper detection.
2. Attach a Listed door tamper switch to protect the cabinet door. Wire the selected device to Zone 6.
Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response.
The 24-hour alarm response must be used for multiple partitioned systems. Enable field 3*17 so that
the system responds to a ground fault on that zone in accordance with the zone type rather than a
ground fault response.
2A. For safe and vault installations, a shock sensor (not supplied) that is Listed for protection of sheet
metal enclosures, as well as an additional Listed tamper switch, must be installed on the cabinet
backbox to protect the cabinet from being removed from the wall. These devices must also be
connected to zone 6.
(Also see Mounting the Cabinet in SECTION 3: Installing the Control).
3. Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.
4. All unused knockouts must be plugged (use the supplied disc plugs and carriage bolts).
5. Must be used with a Listed burglar alarm sounding device/housing. Depending on the application, a
compatible Listed sounding device enclosure may also be required.

UL365 Police Station Connected Burglar Alarm

Follow the instructions for UL609 local installations given above.
For Systems without Line Security:
You may use the control panel's main dialer alone, or the 7845i-ent, 7845-GSM or 7845i-GSM
Communications Device alone.
When using the dialer, program it to send Burglary Alarm, Low Battery and Communicator Test
reports. Field *27 must be set to "0024" (or less) so that test reports are sent at least once every 24
hours.
For Systems with Line Security:
The dialer must be used in conjunction with a 7845i-ent Communications Device.

UL1610 Central Station Burglary Alarm

Follow the instructions for UL365 local installations stated above, and follow the additional guidelines
below.
For Systems without Line Security:
You must use the control panel's main dialer in conjunction with a 5140DLM, 7845i-ent, 7845i-GSM, or
7845GSM Communications Device.
Program the dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.
For Systems with Line Security:
Follow the instructions for Systems without Line Security, but note that only a 7845i-ent may be used as the
secondary Communications Device.
A-2