Honeywell VISTA-128FBPN Installation And Setup Manual page 42

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
Transmitter Input Types
All transmitters have one or more unique factory-assigned input (loop) codes. Transmitters can be programmed as one
of the following types:
Type
RM (RF Motion)
RF (Supervised RF)
UR (Unsupervised RF)
BR (Unsupervised
Button RF)
Transmitter Battery Life
Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific
wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature
may all reduce the actual battery life in a given installation.
The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point within the system.
Compatible 5800 Series Transmitters
Model
5800CO
5817CB
5869
5806W3
5808W3
5809
3-20
Description
Sends periodic check-in signals, fault and low-battery signals. The control panel automatically restores the
zone to "ready" after a few seconds. It is intended for facilities with multiple motion detectors that may fault
and restore simultaneously. The transmitter must remain within the receiver's range.
NOTE: RF Motion may only be used on loop 1 of a door/window type transmitter.
Sends periodic check-in signals, fault, restore, and low-battery signals. The transmitter must remain within
the receiver's range.
Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The
transmitter may be carried off-premises.
These send only fault signals. They do not send low-battery signals until they are activated. The
transmitter may be carried off-premises. Not applicable in Commercial installations.
Product
Carbon Monoxide Detector with Built-in Wireless Transmitter
Commercial Wireless Transmitter
Holdup Switch Transmitter
Photoelectric Smoke Detector with Built-in Wireless Transmitter
Photoelectric Smoke/Heat Detector with Built-in Wireless Transmitter
Rate-Of-Rise Heat Detector
Input Type
RF
RF
RF
RF
RF
RF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-128fbpVista-250fbp

Table of Contents