RUN BELL WIRES
IN CONDUIT
PLATE
PLUG THESE
KNOCKOUTS
PLUG THIS
KNOCKOUT

Mercantile Safe and Vault Listing Guidelines

Follow the guidelines given above for Mercantile
Premises listing.
For safe and vault installations, a shock
sensor (not supplied) that is Listed for
protection of sheet metal enclosures, as well
as an additional Listed tamper switch, must

Commercial Fire Guidelines

For Commercial Fire installations, the following
requirements apply (See Figure 3-3).
System components mounted inside the cabinet
must be placed so that all power-limited wiring is
separated from all non-power-limited wiring by ¼-
inch (6.4mm).
Non-power-limited wiring that exits the control
panel (i.e., transformer wiring) must be run in
conduit.
All unused knockouts must be plugged.
All wiring that exits the control panel must be
strain-relieved (e.g., tie-wrapped).
3-2
PLUG THIS
KNOCKOUT
PC
BOARD
CABINET
MOUNTING
PLUG THIS
SCREWS
KNOCKOUT
(3)
RUN ALL REMAINING
WIRE THROUGH HERE

Figure 3-2: Cabinet Attack Resistance Considerations

TO PLUG AN UNUSED KNOCKOUT OPENING,
REMOVE KNOCKOUT AND INSTALL A PAIR OF
DISC PLUGS AND A CARRIAGE BOLT AS SHOWN.
KNOCKOUT
OPENING
HEX NUT AND
WASHER
be installed on the cabinet backbox to protect
the cabinet from being removed from the wall.
These devices must also be connected to zone
6.
PLATE
WIRES MUST BE
RUN IN CONDUIT
FROM
TRANSFORMER
NOTE: ALL POWER-LIMITED
BATTERY
WIRING MUST BE SEPARATED
FROM NON-POWER LIMITED
AND HIGH VOLTAGE WIRING
BY 1/4-INCH (6.4 mm)
Figure 3-3: Commercial Fire Installation
Considerations
DISC PLUGS (DIMPLES IN DISC
PLUG SHOULD REGISTER INSIDE
KNOCKOUT OPENING)
CARRIAGE BOLT
CABINET SIDE WALL
(OUTSIDE)
fire_burg_cab-001-V0
TELCO
LINE
PC
BOARD
TIE WRAPS
TIE WRAPS
TIE WRAPS
BATTERY
ZONE
WIRING
fire_burg_cab-003-V0