Using a Relay to Unlock a Door
This control can be programmed so that a user can
trigger a relay for 2 seconds (e.g., to unlock a door) by
entering the User Code + [ 0 ].
To program a relay for this purpose, perform the
following steps:

Programming for Communicator

Program the communications device in Device
Programming in the #93 Menu Mode
Programming.
Program field ✳56: Selects the time the panel
should wait before it attempts to send a message to
the second destination.
Program field 1✳70 Event Log Types (1=enable;
0=disable for each type).
Program field 1✳71 12/24-Hour Time Stamp
Format (0=12 hr; 1=24 hr).
Step
Action
1
Enter Output Programming in the #93 Menu
Mode.
2
Program the output type as 1 or 2.
3
For type 1, program the ECP address and
relay number.
4
For type 2, program the house and unit codes.
5
Program the relay number in field 1∗76
(partition-specific).
NOTE: Cannot be used on partition 1 in
Commercial Fire installations.
See Output Programming in the Programming Guide
for a detailed explanation.
Program field ✳57: Selects the initial reporting
destination for messages.
Program field ✳58: Selects events for the primary
sub's ID.
Program field ✳59: Selects events for the secondary
sub's ID.
Program field 1✳72 Event Log Printer On-line
(0=disable; 1=enable).
Program field 1✳73 Printer Baud Rate (1=300;
0=1200).
Section 4 – Programming
4-9