Figure 3-5: Keypad Connections to Control Panel

Commercial Fire Requirements
For commercial fire installations, the primary fire
keypad must be installed on panel Keypad Port 2 and
mounted within 3 feet of the control panel. External
wiring must be run in conduit.
Additionally, you can install supplemental fire keypads
and devices on ECP Port 1, using an ECP Isolator to
separate all fire wiring from all burglary wiring (see
Figure 3-6).
V1 Out (Red)
V2 Out (Red)
TO
GND (Black-)
BURGLARY
DEVICES
PANEL KEYPAD PORT
11
12

Figure 3-6. ECP Isolator Wiring

Installing External Sounders

The VISTA-128FBPN provides two Notification Appliance Circuits for operating fire and burglary alarm notification
appliances. Each circuit is rated as Special Application for Fire and 10VDC – 14VDC, 1.7A max. power-limited for
Burglary.
NOTE: The total alarm current drawn from Auxiliary Power 1, Auxiliary Power 2, polling loop, Bell 1, and Bell 2 cannot
exceed 2.3A for battery-independent operation.
The outputs have the following options:
Selectable to activate by individual zone assignments
Selectable for confirmation of arming ding.
Selectable to chime when entry/exit or perimeter zones are faulted.
Selectable for no timeout or timeout of 2-30 minutes.
3-4
KEYPADS
ECP ISOLATOR
TB1
1
V1 Out (500ma)
2
V2 Out (500ma)
3
GND
4
G (Green)
G
5
Y (Yellow)
Y
1
2
3
4
TB2
13
14
Y (Yellow)
G (Green)
TO
FIRE
GND (Black -)
DEVICES
12V (Red +)
ECPISO-001-V0
Addressing the Keypads
The keypads will not operate until they are
physically addressed and enabled in the
system's Device Programming in the #93 Menu
Mode.
Set each keypad for an individual address (00-30)
according to the keypad's instructions. Set an alpha
keypad for address 00 and other keypads for higher
addresses (00 and 01 are enabled in the system's
default program). Any keypads set for address 02 and
above will appear blank until they are enabled in the
system's program. Each keypad must be set for a
different address.
• Do not set any keypads to address 31
(nonaddressable mode). They will interfere
with other keypads (as well as other devices)
connected to the keypad terminals.
• If an "OC" or "OPEN CIRCUIT" message is
present on a keypad, data from the control is
not reaching the keypad. Please check your
wiring.