Appendix A: Regulatory Agency Statements; Ul Installation Requirements; Ul864/Nfpa Local Fire; Ul864/Nfpa Central Station And Remote Station Fire - Honeywell VISTA-32FBPT Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-32FBPT:
Table of Contents

Advertisement

Appendix A: Regulatory Agency Statements

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

UL Installation Requirements

The following requirements apply to UL commercial burglary installations:
1.
All partitions must be owned and managed by the same person(s).
2.
All partitions must be part of one building at one street address.
3.
The audible alarm device(s) must be placed where it/they can be heard by all partitions.
4.
The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the
cabinet door (supplied with VISTA-32FBPT). Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program
this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response
must be used for multiple partitioned systems.
5.
Remote downloading and auto-disarming are not UL Listed features.

UL864/NFPA Local Fire

Configure at least one Notification Appliance Circuit for supervision and wire polarized fire alarm indicators to it.

UL864/NFPA Central Station and Remote Station Fire

1.
Size the backup battery for 24-hour standby time.
2.
For central station service, you may use the 7845i-ent, 7847i, or IGSMV/IGSMHS communications device alone, the main
dialer with a communications device, or the main dialer with the 5140DLM Backup Dialer Module. For remote station
service, you must use the main dialer with the 5140DLM Backup Dialer Module.
3.
When the main dialer is used, enable it (field 3
(type 19) to system Zone 974 to enable main dialer supervision. The control panel will activate the trouble trigger when it
detects a main dialer supervision fault.
4.
When the backup dialer is used, install it on the control panel's PCB shield as indicated in the Summary of Connections
diagram. Enable it (field 3
system Zone 975 to enable backup dialer supervision.
5.
When the dialer is used, program it to send fire alarm, fire supervisory (if used), trouble, AC loss, low battery, normal
dialer test, and off-normal dialer test reports. Field
once every 24 hours.
6.
If a secondary number is programmed, set the maximum number of dialer retries to 3, 4, or 5 in field 3

Commercial Burglary Requirements

The following requirements apply to all UL Commercial Burglary installations:
1.
All partitions must be owned and managed by the same person(s).
2.
All partitions must be part of one building at one street address.
3.
The audible alarm device(s) must be placed where it/they can be heard by all partitions.
The control cabinet must be protected from unauthorized access. This can be done by installing a tamper
4.
switch on the cabinet door (supplied). See additional requirements below.
U L
This system may be used in installations that require UL2050 compliance.
UL609 Local Mercantile Premises/Local Mercantile Safe & Vault
1.
All zones must be configured for EOLR supervision (
enable tamper detection.
2.
Attach a Listed door tamper switch to protect the cabinet door. Wire the selected device to Zone 6. Program this zone for
day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used
for multiple partitioned systems. Enable field 3
accordance with the zone type rather than a ground fault response.
3.
For safe and vault installations, a shock sensor (not supplied) that is Listed for protection of sheet metal enclosures, as well
as an additional Listed tamper switch, must be installed on the cabinet backbox to protect the cabinet from being removed
from the wall. These devices must also be connected to zone 6.
(Also see Mounting the Cabinet in SECTION 3: Installing the Control).
30) and connect it to a telephone line. Assign a 24-hour trouble response
30) and connect it to a separate telephone line. Assign a 24-hour trouble response (type 19) to
17 so that the system responds to a ground fault on that zone in
27 must be set to "024" maximum so that test reports are sent at least
41=0). If 4190SN V-Plex devices are used, set field
77
21.
24 to "0" to