Mercantile Premises Listing Guidelines

For compliance with the Mercantile Premises Listing, use the following
guidelines:
The panel door must be supervised. Use the supplied door tamper switch
l
and connect it to the T-LID terminal on the control panel.
Use a bell with a tamper-protected housing such as the AB12M Bell/Box.
l
The bell housing's tamper switch and inner tamper linings must be wired to
the hardwire zones on the control panel.
Assign the tamper's hardwire zone to a burglary area. Program the
l
hardwire zone as Trouble by Day/Alarm by Night if only one burglary area is
used. Program it as 24-Hour Audible Burglary if more than one burglary
area is used.
All wiring between the bell and panel must be run in conduit. Remaining
l
wires do not need to be run in conduit.
All wiring that is not run in conduit must exit from the knockout openings on
l
the bottom or back of the cabinet.
All unused knockouts must be plugged using disc plugs (washers) and
l
carriage bolts. To plug an unused knockout opening, remove the knockout
and install a pair of disc plugs and a carriage bolt as indicated in the diagram
below.
A
E
D
C
A
Disc plugs (dimples in disc
plugs must register inside the
knockout opening)
B
Carriage bolt
C
Cabinet wall (outside)
800-23044 Rev.  A draft_11
B
Installation and Setup Guide
D
Hex nut and washer
E
Knockout opening
31