Program feature or option
27 TEST REPORT
INTERVAL
28 POWERUP IN
PREVIOUS STATE
37 DOWNLOAD
COMMAND ENABLES
41 NORMALLY
CLOSED OR EOLR
(ZONES 3-8)
42 DIAL TONE PAUSE
44 RING DETECTION
COUNT
54 UNATTENDED
MODE
56 DYNAMIC
SIGNALING DELAY
77 AUTO TROUBLE
RESTORE
80 ZONE TYPE
RESTORES FOR TYPES
9, 10 & 14
1 12 PROGRAM
NOTIFICATION SIGNAL
1 13 SYSTEM SENSOR
REVERSING RELAY
1 18 AFFECTS LOBBY
1 19 ARMS LOBBY
1 22 thru 1 25 CROSS-
ZONING PAIRS (1 – 4)
1 28 RF TRANSMITTER
LOW BATTERY SOUND
1 29 RF TRANSMITTER
LOW BATTERY
REPORTING
x
Possible settings
Permitted in
UL864? Y/N
Enter 0001-9999 for the test
Y
report interval in hours.
Enter 0000 for test reporting.
0 = disable
Y
1 = enable
0 = disable
N
1 = enable
0 = EOLR supervision
N
1 = N.C. loops
Enter the wait time for dial
Y
tone detection:
0 = 5 seconds; 1 = 11 seconds;
2 = 30 seconds.
Enter 00 to disable ring
N
detection.
Enter 01-14 for ring counts of
1-14.
Enter 15 to select Answering
Machine Defeat Mode
0 = disable
N
1 = enable
Enter 00-15 times 15 seconds.
Y
0 = disable
Y
1 = enable
0 = disable
N
1 = enable
0 = no
Y
1 = yes
N
0=use neither Zone 1 or Zone
2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2
inputs.
0 = disable
N
1 = enable
0 = disable
N
1 = enable
Enter 001-128
N
Enter 000,000 to disable
0 = disarmed state only
N
1 = both armed and disarmed
states
0 = disable
N
1 = enable
Settings permitted in UL 864
Must be set to "0024"
(Maximum 24 hours)
Must be set to "1" (enable).
Must be set to "0" for all
entries (disable).
Must be set to "0" (EOLR
Supervision).
Must be set to "0" (5 seconds).
Must be set to "00" (disable).
Must be set to "0" (disable).
Must be set to "6" (90
seconds).
Must be set to "1" (enable).
Must be set to "1" (enable) for
zone type 9.
Must be set to "1" (yes).
Not Used. Must be set to "0".
Must be set to "0" (disabled)
for partition 1.
Must be set to "0" (disabled)
for partition 1.
Must be set to "000,000"
(disabled) for fire zones.
Must be set to "1" (both
armed and disarmed states).
Must be set to "1" (enable).