Field *04 must be enabled for randomization. A user
must initiate a random schedule by entering one of the
following sequences:
[User Code] + [#] + [41]. This will randomize, up
to 30 minutes, the activation time of all devices,
programmed for randomization, assigned to the
partition the sequence is entered in. Enter the
sequence again to turn off the random schedule.
[User Code] + [#] + [42]. This is the same as the
method above, except the randomization occurs
only on devices with activation times within 6 PM
and 5 AM. Enter the same sequence again to turn
off the random schedule.
You must not program Random Scheduling of
U L
Time Driven Events for UL installations.
PROMPT
Timed Events ?
1 = YES 0 = NO
0
TIMED EVENT # ?
01-20, 00=Quit 01
01 ACTION ?
none
00
ACTION CODES
01=Relay On
02=Relay Off
03=Relay Close for 2 seconds
04=Relay Close XX minutes
05=Relay Close YY seconds
06=Relay Group On
07=Relay Group Off
08=Relay Group Close for 2
seconds
09=Relay Group Close XX
minutes
10=Relay Group Close YY
seconds
20=Arm-STAY
21=Arm AWAY
22=Disarm
23=Force Arm STAY
24=Force Arm AWAY
25=Arm INSTANT
26=Arm MAXIMUM
40=Enable Open Window by
Part.
41=Enable Close Window by
Part.
EXPLANATION
Enter 1 to program timed events.
Enter the timed event number to be programmed (01-20).
Press [✳].
The system then prompts the user to enter the desired action to be taken.
Enter 00 at the "TIMED EVENT #?" prompt to quit the timed event menus and display the "Quit ?" prompt.
Enter the action code for this timed-event number from the list at the left. This could be an output command,
an arming command, or any other Time-Driven event.
Press [✳] to accept the entry. The prompt for the action specifier appears.
EXPLANATION
Actions 01-05
If you selected actions 01-05, the prompt at the right appears. Enter the relay
number.
Press [✳] to accept entry. The "Time Window ?" prompt appears.
Actions 06-10
If you selected actions 06-10, the prompt at the right appears. Enter the relay
group number.
Press [✳] to accept entry. The "Time Window ?" prompt appears.
Actions 21-26 and 40-41
If you selected actions 21-26 or 40-41, the prompt at the right appears. Enter
the partition to which the action applies. Enter 0 to select all partitions. Enter
a partition number again to deselect it.
Press [✳] to accept entry. The "Time Window ?" prompt appears.
Section 6 – Scheduling Options
Time-Driven Event Programming
The following menu items must first be programmed in
Output Programming in the #93 Menu Mode:
Enter Relay No.
(reference identification number)
Output Group
(if applicable)
Restriction (#70)
(Restriction must be set to yes for
Commercial Fire installations.)
Output Type
(V-Plex or 4204/4204CF)
Zone No.
(V-Plex)
ECP Address
(4204/4204CF)
Relay No.
(4204/4204CF)
After entering Scheduling Menu Mode, press [0] until
the "Timed Events ?" prompt appears.
ACTION SPECIFIER
01 RELAY # ?
00
01 RELAY GRP # ?
00
PART? 12345678
HIT 0-8
X X
6-9