FIELD
TITLE and DATA ENTRIES
Zone Bypass After Disarm
1*11
0 = disable
1 = enable
Program Notification Signal
1*12
0 = no
1 = yes
System Sensor Reversing Relay
1*13
0 =use neither Zone 1 or Zone 2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
Cancel Verify
1*15
0 = disable
1 = enable alarm output pulse upon kissoff of
Cancel report.
Lobby Partition
1*17
0 = none; 1-8 = partition number
Affects Lobby (partition-specific)
1*18
0 = disable
1 = enable
Arms Lobby (partition-specific)
1*19
0 = disable
1 = enable
Exit Delay Reset
1*21
0 = disable
1 = enable
UL
Exit Delay Reset is not suitable for use in a UL installation (must be 0).
Cross-Zoning
UL
Cross Zoning is not suitable for use in a UL installation.
5-8
EXPLANATION
Enter 1 for each partition in which zones will remain bypassed after disarm.
NOTES:
For each partition in which field 1✳11 is enabled, the USER CODE + OFF will
no longer unbypass zones. To unbypass ALL zones, you must enter USER
CODE + # + 64. To unbypass zones INDIVIDUALLY, you must enter USER
CODE + 6 + zone number.
Any zone that was automatically bypassed by the system will be unbypassed
upon disarming of the system (e.g., STAY mode, Auto-STAY, etc.).
Vent zones and zones bypassed by a programmed Auto-Bypass schedule
(Timed Driven Event) are considered "manual bypasses" and will not be
unbypassed upon disarming the system.
Zones that were in a bypassed state at the time a System Shutdown is sent
from the Compass Downloading software will be unbypassed when the
System Shutdown is removed.
If enabled, sends signal to central station indicating the system has been put
in programming mode.
Must be 1 for Commercial Fire installations.
Selects zones for system sensor reversing relay.
Not Used.
NOTE: Field 1✳52 must be enabled to send a Cancel report to the central
station.
Select the Common Lobby Partition.
If enabled, causes lobby partition to disarm when this partition disarms.
NOTE: This partition must be armed before lobby can be armed.
If enabled, arming this partition causes the system to attempt to arm the lobby
partition. Field, field 1*18 must also be enabled (partition-specific).
NOTES:
The lobby cannot be armed unless all partitions programmed for "affect" (field
1*18) is already armed.
If this field is enabled, Field 1*18 for this partition must also be enabled.
If enabled, when the panel is armed, the normal exit delay begins. After the
user exits, closes the door and then re-enters the premises, the exit delay
time is reset to the programmed value.
NOTES:
Exit Delay Reset is designed to allow an operator to re-enter the premises to
retrieve a forgotten item without triggering an alarm.
This feature may only be activated once after arming. The Exit Delay must be
enabled for SIA installations.