Section 12 : Agency Statements; Ul Installation Requirements; Safe & Vault; Ul365/Ul609 Bank Safe And Vault Alarm System - Honeywell VISTA-128BPT Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-128BPT:
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

UL Installation Requirements

The following requirements apply to both UL
Residential and UL Commercial Burglary installations:
All partitions must be owned and managed by the
same person(s).
All partitions must be part of one building at one
street address.
The audible alarm device(s) must be placed where
it/they can be heard by all partitions.
The control cabinet must be protected from
unauthorized access. This can be done by
installing a tamper switch on the cabinet door
(not supplied with VISTA-128BPT/VISTA-250BPT)
or by installing a UL Listed passive infrared
UL609 Local Mercantile Premises/Local Mercantile Safe & Vault
Use the following guidelines for a Local Mercantile Premises/Local Mercantile Safe & Vault installation:
All zones must be configured for EOLR
supervision (∗41=0). Wireless sensors may not be
used. If 4190WH V-PLEXs are used set field ∗24
to "0" to enable tamper detection.
Attach a door tamper switch (supplied) to the
VISTA-128BPT/VISTA-250BPT cabinet backbox.
For safe and vault installations, a shock sensor
(not supplied) must also be attached to the
backbox. (Also see SECTION 3: Installing the
Control)

UL365/UL609 Bank Safe and Vault Alarm System

Follow the instructions for UL609 local
installations above and Bank/Mercantile Safe and
Vault (page 59) sections of this manual.
Bell 1 Confirmation of Arming Ding (∗16) must be
set to 1 to on (enabled) (will automatically test
bell).
Entry delays or any other delays to report alarms
may not exceed 45 seconds.
Models 7847i, 7847i-E, IGSMV, and IGSMHS

Section 12 : Agency Statements

detector positioned to detect cabinet access. Wire
the selected device to any EOLR-supervised zone
(Zone 1-8). Program this zone for day
trouble/night alarm (type 05) or 24-hour audible
alarm (type 07) response. The 24-hour alarm
response must be used for multiple-partitioned
systems.
Remote downloading and auto-disarming are not
UL Listed features.
NOTE: UL Commercial Burglary installations
Wire an ADEMCO AB12M Bell/Box to the bell
output. Bell wires must be run in conduit. Program
the bell output for a timeout of 16 minutes or
longer timeout and for confirmation of arming
ding. (Also see SECTION 3: Installing the Control.)
Wire the VISTA-128BPT/VISTA-250BPT tamper
switch and AB12M Bell/Box tamper switches to
any EOLR-supervised zone (zones 1-8). Program
this zone for day trouble/night alarm (type 05) or
24-hour audible alarm (type 07) response. The
24-hour alarm response must be used for
multiple-partitioned systems.
Entry delays must not exceed 45 seconds, and
exit delays must not exceed 60 seconds.
Bell Timeout must be programmed for 16 minutes
min.
Two 17.2AH Batteries must be used for this
application.
The main protective circuits, linings and
attachments on the safe and vault, control units
and alarm housing must be of the normally closed
circuit, fully supervised type.
To be installed inside the safe or vault.
12-3
require the attack resistant cabinet. The
cabinet is included in the VISTA-ULKT kit.