Guidelines For Wiring A System - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

Event Log
Provides an event log (history log) that can store up to 512 events.
Can view the event log on an alpha keypad.
Fire Walk-Test Mode
Provides an automatic test of integrated V-Plex devices that have the automatic test feature.
Can display all fire zones that remain untested.
Can log test results in the event log.
Can report the test results to the central station.
Additional Features
Provides two style-Y supervised Special Application Notification Appliance Circuits.
Provides an auxiliary relay (form C) that can activate alarms troubles/supervisories, reset 4-wire smoke detectors, or
as a battery saver (removes power from non-critical loads 4 hours after AC power loss).
Provides up to 60 installer-defined, custom words that can be used for zone descriptors.
Provides 35 keypad macro commands (each macro is a series of keypad commands of up to 32 keystrokes) using the
A, B, C, and D keys by partition.
Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm unless
its cross-zone is also faulted within a 5-minute period.
Contains a built-in User Manual, which provides the end user with a brief explanation of the function of a key when
the user presses any of the function keys on the keypad for 5 seconds.
Provides trigger outputs, which may interface with Communicator equipment or other devices such as keyswitch
LEDs, or printer.
Provides an option to have trouble and supervisory conditions to automatically clear from the display when the zone
returns to the ready/normal state (entry of Code + OFF is not required).
Provides Maintenance Signal support for certain smoke detectors (5192SD, 5192SDT, 5193SD, 5193SDT).
At least one 2-line alpha keypad (6160/6160CR-2) must be connected to the system for programming (if you are
using keypad programming), and must remain connected to the system in order to allow the primary user to program
additional user codes into the system at a later time.

Guidelines for Wiring a System

The installer must keep certain guidelines in mind while installing a system. The Vista-128FBPN contains an ECP bus
and a polling loop bus for connecting Fire and Burglary devices. When installing a Fire ONLY system or Burglary ONLY
system both busses may be used interchangeably. When installing a Commercial Fire and Burglary System all Fire
devices must be isolated from the Burglary devices. This is accomplished by using an isolator as shown in Figure 1-1.
Additionally, in Commercial Fire installations, the primary keypad must be connected to Keypad Port 2 mounted within
20 feet of the control panel, and wired in conduit.
A fault on an SLC may disable all NACs on that circuit therefore only one NAC per SLC circuit may be used.
Synchronization is based on the individual zone output basis only, not between each sync module.
synchronization between the individual sync modules.
Notification Appliance Circuit (NAC) must be wired and isolated or Riser Conductors must be installed in accordance
with the survivability from attack by fire requirements in the National Fire Alarm Code, NFPA 72.