Communicators Connected To The Ecp - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide

Communicators Connected to the ECP

The control can support an IP or GSM communications device (7845i-ent, 7845i-GSM, or 7845-GSM) that connects to
control panel's keypad terminals. All messages programmed for transmission via the phone lines may also be sent via
the communications device. These messages are transmitted in Contact ID format regardless of the format programmed
for the control in fields 45 and 47.
We recommend that, if possible, you use Contact ID for the main dialer. If Contact ID is not used, certain types of
reports are not sent.
Supervision
The data lines between the control and the communications device, as well as certain functions in the Communicator,
can be supervised. If communication is lost or a trouble condition occurs, both the communications device and the
control's dialer can be programmed to send a Trouble message to the central station.
NOTE: For complete information, see the Installation Instructions that accompany the Communicator.
Operation
The VISTA-128FBPN features Dynamic Signaling Delay and Dynamic Signaling Priority message reporting when
a Communicator is used. These message outputs are accessed through data fields ✱56 and ✱57, respectively. The
Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the central station.
The feature is described as follows:
Dynamic Signaling Delay (Field ✱56)
Select the time the panel should wait for acknowledgment from the first reporting destination before it attempts to send
a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments.
Dynamic Signaling Priority (Field ✱57)
Select the initial reporting destination for messages, Primary Dialer (0) or Communicator (1).
The chart below provides an explanation of how the Dynamic Signaling feature functions.
If Priority
And message is...
(✱57) is...
Primary Phone
Acknowledged before delay expires Message is removed from queue and no message is sent to
No. ("0")
Not acknowledged before delay
expires
Communicator
Acknowledged before delay expires Message is removed from queue and no message is sent to
("1")
Not acknowledged before delay
expires
Additional communications device reporting options are defined by selecting the events for each subscriber ID in fields
58 and 59. The reporting events are Alarms, Troubles, Bypasses, Openings/Closing, System Events, and Test. Also,
within an enabled category, the specific event must be enabled for dialer reporting. If, for instance, zone 10 is enabled to
report, but zone 11 is not, zone 10 will report via the communications device, but zone 11 will not.
Messages are transmitted from the VISTA-128FBPN to the communications device on a "first in/first out" basis. If
events occur at the same time, they are transmitted in order of priority. The priority from most to least important is :
Fire Alarms, Panic Alarms, Burglary Alarms, Fire Troubles, Non-Fire Troubles, Bypasses, Openings/Closings, Test
messages, and all other types of reports.
There are two subscriber ID's programmed into the communications device: primary and secondary. These correspond to
the two subscriber ID's programmed into the control for each partition. If a subscriber ID for a partition is not
programmed (disabling reports to that central station), the events enabled for the corresponding subscriber ID in the
communications device will not be transmitted.
When the Communicator is being used, *51 dual reporting should not be used.
If split reporting is selected for the VISTA-128FBPN, then the communications device will send the appropriate reports
to the primary and secondary central stations.
3-24
Then...
communications device.
Message is sent to both the Primary Phone No. and
communications device.
Primary Phone No.
Message is sent to both the Primary Phone No. and
communications device.