Compatible Polling Loop Devices
Model Number
Type
4297
Extender Module
4208SN
8 Zone V-Plex Interface
4208SNF
8 Zone V-Plex Class A Interface
269SN
V-Plex Holdup Switch
5192SD
Photoelectric Smoke Detector Devices
5192SDT
Photoelectric Smoke Detector w/Heat Detector
5193SD
Photoelectric Smoke Detector Device
5193SDT
Photoelectric Smoke Detector w/Heat Detector
4101SN
Serial Number Single-Output Relay Module
4208U
Universal 8-Zone Expander
4959SN
Aluminum Overhead Door Contact
4193SN
Serialized 2-Zone Expander
4293SN
Serialized 1-Zone Expander
4190SN
Serialized 2-Zone Expander
4190WH
DIP Switch 2-Zone Expander
998MX
Serialized PIR
Quest 2260SN
Serialized PIR
IS2500SN
V-Plex PIR
V-Plex VSI
V-plex Short Isolator
NOTE: If using the new 5193SD/SDT V-Plex smoke detectors (or older 5192SD/SDT with the maintenance DIP sw enabled)
the "Smart" option must be selected in zone programming or when they
smoke goes into a High Sens or Low Sens condition.
To install polling loop devices, perform the following steps:
Step
Action
1
Select devices from the list of compatible devices shown previously.
2
Set the DIP switches in the device (if required). Refer to the device's instructions for the DIP Switch Tables.
3
Mount each device in the desired location. Refer to the device's instructions.
4
Run wires from the control panel to each device on the polling loop (see Figure 3-15). No individual wire run
may exceed the lengths shown in the following table.
Maximum Polling Loop Wire Runs
Wire Gauge
#22 gauge
#20 gauge
#18 gauge
#16 gauge
5
Wire each device to the polling loop, making sure of the correct polarity (refer to the device's instructions).
NOTE: If you are using serial number devices, and intend to enroll each device through the keypad
automatically, wire no more than 25 of these devices to the control at a time. Then power up and
program them before connecting the next 25. Leave previously enrolled devices connected.
If you intend to manually enter the serial numbers through the keypad or through Compass downloading
software, all the devices may be connected before powering up to program.
Max. Length
650 feet
950 feet
1500 feet