Trouble Conditions - Honeywell VISTA-128FBPN Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide

Trouble Conditions

Supervisory Messages
Display
Description
SUPV +
This indicates that a fire supervisory
Zone
condition exists on the zone number
Number
displayed. This means that the operation
of the fire alarm system may be
compromised.
Check or Trouble Messages
Display
Description
CHECK or
This indicates that a problem exists on
TRBL
the zone number displayed. Zone trouble
may be caused by one of the following
(as per field
conditions:
3✳00)
A hardwired fire zone is open
(broken wire).
A Day/Night zone (zone type 5) is
faulted.
A polling loop zone is not seen by
the control panel.
A polling loop zone has been
tampered (cover removed on a
4190SN).
A wireless zone has not checked in
during the time programmed in field
1✳31.
A 5800 Series transmitter has been
tampered (cover removed).
CHECK 6XX
This indicates a trouble on a 4204CF
XX = 01-32
Supervised Notification Appliance Circuit
(corresponding relay number 01-32).
CHECK 8XX
This indicates a trouble on a peripheral
XX = 00-30
device (connected to the panel's keypad
terminals) of the corresponding device
address (00-30).
CHECK 9XX
This indicates that a system trouble
XX = 70-77,
exists (RF receiver, Notification
88,90,97
Appliance Circuit, etc.).
If the problem has been corrected, enter an
OFF sequence (Security Code + OFF) twice
to clear the display.
Power Failure
Display
Description
AC LOSS
This indicates that the system is
operating on battery power only. Check
POWER
to see that the circuit breaker for the
LED is off
branch circuit that your system's
transformer is wired to has not been
accidentally turned off. Instruct the
user to call a service representative
immediately if AC power cannot be
restored.
10-4
Other System Messages
Display
Description
COMM
Indicates a failure occurred in the
FAILURE
telephone communication portion of your
system.
LO BAT
Indicates a low-battery condition exists in
the wireless transmitter displayed.
Pressing any key silences the audible
warning sound.
SYSTEM
This indicates that a low-battery condition
LO BAT
exists with the system's backup battery.
HSENS
Indicates a smoke detector with a high
sensitivity level, which may cause a false
alarm. The detector should be cleaned or
replaced.
LSENS
Indicates a smoke detector with a low
sensitivity level. The detector may not
detect a smoke condition. The detector
should be cleaned or replaced.
RCVR
Indicates the system has more wireless
SETUP
zones programmed than the RF receiver
ERROR
can support. If this is not corrected, none
of the zones in the system will be
protected. If additional wireless zones are
desired, use an appropriate receiver.
MODEM
This indicates that the control is on-line
COMM
with a remote computer.
System Off-Normal Report
If programmed, an Off-Normal report is generated
instead of the periodic test report if any of the following
conditions are present at the time of the report:
Fire trouble on any zone (zone types 9, 16, 17, 18)
Fire supervisory present (zone type 18)
Unrestored fire alarm on any zone
Bypass of any fire zone
A fault for any supervised fire Notification
Appliance Circuit
Bypass/disable of any supervised fire Notification
Appliance Circuit
Telco fault of either dialer line
Bypass/disable of either dialer line
Earth ground fault
Bypass of earth ground supervisory zone
Fault on LORRA "XMIT OK" signal (if enabled)
LORRA trigger bypassed
AC failure
Low system battery
Keypad supervision fault
The Off-Normal report is sent as follows:
Contact ID: Code 608
High Speed: Channel 3 of system report used
(channel 9=6)
Low Speed: Digits programmed in System Group
#4 report codes