Honeywell VISTA-128FBPN Installation And Setup Manual page 64

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Entry Delay #1 (partition-specific)
*09
Enter 02-15 multiplied by 15 seconds.
00 = 240 seconds (4 minutes).
Exit Delay #1 (partition-specific)
*10
Enter 03-15 multiplied by 15 seconds.
Entry Delay #2 (partition-specific)
*11
Enter 02-15 multiplied by 15 seconds.
00 = 240 seconds (4 minutes).
Exit Delay #2 (partition-specific)
*12
Enter 03-15 multiplied by 15 seconds.
Bell 1 Timeout
*13
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
Trigger or RS232 Input
*14
0 = trigger
1 = RS232 input
Keyswitch Assignment
*15
Enter 1-8 partition keyswitch is being used.
Enter 9 if the keyswitch is being used to
silence fire Notification Appliance Circuits in
the event of a fire alarm.
Enter 0 if the keyswitch is not used.
Bell 1 Confirmation of Arming
*16
Ding (partition-specific)
0 = disable
1 = enable
AC Loss Keypad Sounding
*17
0 = disable
1 = enable
5-2
EXPLANATION
Entry delay defines the delay time that allows users to re-enter the premises
through a door that has been programmed as an entry delay door and disarm
the system without sounding an alarm. The system must be disarmed within
this period or an alarm will occur. During entry time a distinct annunciation is
produced upon entry to warn the person entering the premise that entry delay
has begun. When the system is in Entry Delay, disarming is accomplished by
entering a valid user code. The annunciation silences upon entry of the first
digit of the user code. If an invalid user code is entered the annunciation
resumes.
NOTE: The delay may not exceed 45 seconds for UL installations. SIA
Guidelines: The entry delay time and Abort Window (field *88) combined
cannot exceed 60 seconds.
Exit delay defines the delay period that allows users to leave the premises
through a door that has been programmed as an entry/exit delay door after
arming the system without setting off the alarm.
NOTE: The delay must be set for a minimum 60 seconds for SIA installations.
Entry Delay #2 is used for a secondary door requiring a longer delay than
those assigned to Entry Delay #1. During entry time a distinct annunciation is
produced upon entry to warn the person entering the premise that entry delay
has begun. When the system is in Entry Delay, disarming is accomplished by
entering a valid user code. The annunciation silences upon entry of the first
digit of the user code. If an invalid user code is entered the annunciation
resumes.
NOTE: The delay may not exceed 45 seconds for UL installations. SIA
Guidelines: The entry delay time and Abort Window (field *88) combined
cannot exceed 60 seconds.
Exit Delay #2 is used for a secondary door requiring a longer delay than those
assigned to Exit Delay #1.
NOTE: The delay may not exceed 60 seconds for UL installations. The delay
must be set for a minimum 60 seconds for SIA installations.
Defines the length of time the Bell 1 Output and the keypad's sounder will
sound for all audible alarms.
Must be minimum 16 minutes for Commercial Burglary installations. Must be
minimum 6 minutes for Commercial Fire and SIA installations.
Select if J2 Pin 5 is being used as Fire Alarm trigger output or as an RS232
input. If set for RS232, this enables the system to receive serial data (75
baud).
NOTE: Must be set to "0" for Commercial Fire installations.
The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer
available as protection zone). The fire and panic alarm voltage triggers (J2)
automatically become ARMING and READY status outputs for the Keyswitch
LEDs.
Openings/closing report as user "0" if enabled in field *40.
If enabled, produces ½-second external alarm sounding ("ding") at the end of
exit delay (or after kissoff from the central station, if sending closing reports).
NOTE: If using a keyfob, when the button is pressed, either for arming or
disarming, the bell will ding indicating that the button is working.
Must be 1 for UL commercial burglary installations.
If enabled, sounding at the keypad (rapid beeping) occurs when AC power is
lost (sounding occurs about 2 minutes after actual AC loss).
Must be 1 for Commercial Fire installations.